Back to search

University of Manitoba

An infrared spectrometer based on a MEMS fresnel zone plate for measuring dissolved gases in high voltage equipment

Abstract

dc:description.abstract

This thesis presents a unique design for an infrared spectrometer based on a MEMS Binary Fresnel Zone Plate for the purpose of assessing the health of oil-impregnated high voltage (HV) equipment. It does so by measuring dissolved gases within it. These gases include carbon monoxide, carbon dioxide, methane, ethane, ethylene, and acetylene. These gases are currently measured using numerous technologies such as gas combustion, gas chromatography, photoacoustic spectroscopy, and FTIR spectroscopy. Each of these technologies have their advantages and disadvantages. The design presented in this thesis consists of an analysis of how the various Binary Zone Plate parameters affect its spectral resolution and transmission efficiency. Simulations show that increasing the number of zones and the focal length, as well as decreasing the aperture diameter, increases the spectral resolution of the spectrometer. Simulations also show that transmission efficiency is proportional to the number of zones and the aperture diameter. This thesis presents a theoretical argument for how one zone plate lens can be used to measure all dissolved gases present in HV equipment. Lenses for the visible and infrared ranges were fabricated in the University of Manitoba NSFL Cleanroom. The lenses were then tested in an optical setup. The results show that the visible light experiments were successful in achieving appropriate spectral discrimination by changing the distance between the aperture and the lens. The results from the infrared experiment show that a detector was able to discriminate between full and no incident radiation.

Degree

thesis:*
Level thesis:degree_level
Master of Science (M.Sc.)
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Year dc:date.issued
2017

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Glowacki, Pawel
Advisor dc:contributor.supervisor
  • Shafai, Cyrus (Electrical and Computer Engineering)
Committee members dc:contributor.committeemember
  • Sherif, Sherif (Electrical and Computer Engineering)
  • Paliwal, Jitendra (Biosystems Engineering)

Subjects

dc:subject × 9

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1993/32165

Chain of custody

source
Harvested from
University of Manitoba
Base URL
mspace.lib.umanitoba.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Glowacki, Pawel. An infrared spectrometer based on a MEMS fresnel zone plate for measuring dissolved gases in high voltage equipment. Master of Science (M.Sc.) thesis, 2017. http://hdl.handle.net/1993/32165