Back to search

University of Manitoba

Evaluation of partial discharge characteristics in inclined plane tracking and erosion tests on silicone rubber under AC and DC voltages

Abstract

dc:description.abstract

Polymer housing material for transmission line insulators offers superior pollution performance compared to glass and ceramic. However, in coastal and high pollution environments polymer insulators are susceptible to accelerated aging caused by electrical tracking and erosion. In the last couple of decades, field and laboratory studies on polymeric insulators have shown that tracking and erosion are more severe for outdoor insulation under DC voltage stress compared to AC stress at similar voltage magnitudes. Therefore, with the increased development in DC mode of power delivery, design of erosion resistant materials to improve the reliability of DC insulation systems has become an important task. This task relies on a thorough understanding of the mechanisms that lead to material erosion. This thesis investigates partial discharge (PD) characteristics of discharges that lead to erosion of silicone rubber (SR) polymer under AC stress and DC stress of both polarities. The experiments are performed on high temperature vulcanized SR material samples. The inclined plane test apparatus, constructed in accordance with IEC 60587 requirements, is employed to produce the surface partial discharges and the resulting accelerated aging of the specimens. Two commercial instruments are used to obtain PD data. A concurrent analysis of visual observations of discharge and partial discharge data is performed to classify discharges based on the severity of material degradation that each type causes. PD characteristics were identified for three types of discharges, using phase resolved PD patterns, PD histograms, and a signal processing technique called Time Frequency mapping. Individual pulse waveshapes of each type of discharge were also analyzed. Amplitude, energy, pulse width, and frequency spectrum were evaluated and compared for the eroding discharge pulses at the three voltage types. It was concluded that greater pulse width and the presence of dominant DC component in the spectrum are attributable to discharges that cause greater severity of SR erosion under DC stress relative to AC.

Degree

thesis:*
Level thesis:degree_level
Master of Science (M.Sc.)
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Year dc:date.issued
2020

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Pevtsov, Valeria
Advisor dc:contributor.supervisor
  • Kordi, Behzad (Electrical and Computer Engineering)
Committee members dc:contributor.committeemember
  • Filizadeh, Shaahin (Electrical and Computer Engineering)
  • Fernando, Namal (Electrical and Computer Engineering)
  • Jacob, Nathan (Manitoba Hydro)

Subjects

dc:subject × 6

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Dc Identifier Citation
V. Pevtsov, N. Jacob, and B. Kordi, “Evaluation of partial discharge characteristics in inclined plane tracking and erosion tests on silicone rubber under ac voltage,” in 2020 IEEE Electrical Insulation Conference (EIC), 2020, pp. 175–178

Chain of custody

source
Harvested from
University of Manitoba
Base URL
mspace.lib.umanitoba.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Pevtsov, Valeria. Evaluation of partial discharge characteristics in inclined plane tracking and erosion tests on silicone rubber under AC and DC voltages. Master of Science (M.Sc.) thesis, 2020. http://hdl.handle.net/1993/35219