Online neutral line fault locator for point-to-point HVdc transmission for line to ground faults

Abstract

dc:description.abstract

High Voltage Direct Current (HVdc) transmission is seeing an increasing use as an efficient method for delivering renewable energy from remote areas to the load center(s). Maintaining the integrity of the HVdc transmission line is paramount to insuring the reliability and the sustainability of the supply. An important component, to this reliability and sustainability, is the rapid detection and repair of faults on the HVdc transmission line. Modern point-to-point HVdc transmission systems utilize a neutral conductor in addition to the power carrying conductors for HVdc power transmission. The voltage of the neutral conductor is normally zero volts since the neutral conductor is grounded at one end. Online dc Line Fault Locator (dcLFL) systems, such as the dcLFL developed by Manitoba Hydro International (MHI), can reliably and rapidly detect the fault location on the main power carrying conductors of an HVdc transmission line. This is accomplished by detecting the arrival time of the traveling wave from the voltage at the station. However, the low voltage on the neutral conductor prevents the dcLFL from detecting fault locations on the neutral conductor. The objective of this research is to design and implement a suitable method for reliably and rapidly detecting and locating faults on the neutral conductor. An online Neutral Line Fault Locator (nLFL) system which uses HVdc system measurements with regression analysis to derive the transmission line impedance to determine an accurate fault location is proposed. To surmount the low-voltage problem. The proposed nLFL system was developed and tested, with a highly detailed Electromagnetic Transients (EMT) simulation model. The nLFL system was constructed in hardware and tested in real time using a real-time EMT simulator. After detailed EMT studies of various scenarios, the nLFL system was field tested on the East Alberta Transmission Line (EATL) HVdc system.

Degree

thesis:*
Level thesis:degree_level
Doctor of Philosophy (Ph.D.)
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Year dc:date.issued
2022

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Williams, Dexter M. T. J.
Advisor dc:contributor.supervisor
  • Gole, Aniruddha M.
Committee members dc:contributor.committeemember
  • Filizadeh, Shaahin (Electrical and Computer Engineering)
  • Rajapakse, Athula (Electrical and Computer Engineering)
  • Gokaraju, Ramakrishna (University of Saskatchewan)
ORCID person:identifier.orcid

Subjects

dc:subject × 5

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1993/36686

Chain of custody

source
Harvested from
University of Manitoba
Base URL
mspace.lib.umanitoba.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Williams, Dexter M. T. J.. Online neutral line fault locator for point-to-point HVdc transmission for line to ground faults. Doctor of Philosophy (Ph.D.) thesis, 2022. http://hdl.handle.net/1993/36686