Back to search

Digital Repository at the University of Maryland

Analyzing Photo-Electric Smoke Detector Response Based On Aspirated Smoke Detector Obscuration

Abstract

dc:description.abstract

Accurate obscuration levels at the response time of photo-electric smoke detectors are needed for proper detection modeling and analysis. In recent works, obscuration meters were used to measure the obscuration level at photo-electric detector response. In this study, aspirated smoke detectors (VESDA) were used to measure this same obscuration level. These detailed measurements were used to reduce the ambient light and the technology difference error associated with the obscuration meters. The use of aspirated smoke detection (VESDA) instead of light obscuration meters displayed increased accuracy for a majority of the experiments conducted in the 2008 report titled "Validation of a Smoke Detection Performance Prediction Methodology" involving flaming and non-flaming incipient fire sources at 3 different ventilation conditions.

Degree

thesis:*
Department dc:contributor.department
Fire Protection Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2010

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Miller, John Herbert Thomas
Advisor dc:contributor.advisor
  • Milke, James A

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1903/10455

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Miller, John Herbert Thomas. Analyzing Photo-Electric Smoke Detector Response Based On Aspirated Smoke Detector Obscuration. Digital Repository at the University of Maryland, 2010. http://hdl.handle.net/1903/10455