Back to search

Digital Repository at the University of Maryland

AN INTEGRAL MODEL FOR TURBULENT FLAME RADIAL LENGTHS UNDER A CEILING

Abstract

dc:description.abstract

An analytical study using an integral model for turbulent flame radial lengths under a ceiling is presented. Dimensionless equations give results in terms of <italic>Q*</italic> -- dimensionless firepower, and <italic>D/H</italic> -- the ratio of fire diameter to ceiling height. The model used an empirical relationship for the mixing ratio of air entrained to stoichiometric air needed for the ceiling jet flame. This value varies from 9.6 for short radial flames to 1 for long flames that tend to become laminar. Predictions from the model are in good agreement with the experimental data from previous work found in the literature. They span a range that contains data where the fire plume flame just touches the ceiling to the case where long ceiling flames become laminar. An alternative empirical fit of the theoretical results finds that the radial flame length is independent of ceiling height once the flame hits the ceiling.

Degree

thesis:*
Department dc:contributor.department
Fire Protection Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2010

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Ding, Haiwen
Advisor dc:contributor.advisor
  • Quintiere, James G

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1903/10495

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Ding, Haiwen. AN INTEGRAL MODEL FOR TURBULENT FLAME RADIAL LENGTHS UNDER A CEILING. Digital Repository at the University of Maryland, 2010. http://hdl.handle.net/1903/10495