Abstract
dc:description.abstractApproximation methods exist to provide estimates of smoke detector response based on optical density, temperature rise, and gas velocity thresholds. The objective of this study was to assess the uncertainty associated with these estimation methods. Experimental data was used to evaluate recommended alarm thresholds and to quantify the associated error. With few exceptions, less than 50 percent of the predicted alarm times occurred within ± 60 seconds of the experimental alarms. At best, errors of 20 to 60 percent (in under-prediction) occurred for smoldering fires using an optical density threshold. For flaming fires, errors in predicted alarm times on the order of 100 to 1000 percent in over-prediction of the experimental alarms were common. Overall, none of the approximation methods distinguished themselves as vastly superior. Great care must be exercised when applying these approximation methods to ensure that the uncertainty in the predicted alarm times is appropriately considered.
Degree
thesis:*- Department dc:contributor.department
- Fire Protection Engineering
- Year dc:date.issued
- 2003
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Geiman, Justin Aaron
- Advisors dc:contributor.advisor
-
- Milke, James A
- Mowrer, Frederick W
- Gottuk, Daniel T
Rights
- Language dc:language.iso
- en_US
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1903/113