Experimental Study of Hybrid Cooled Heat Exchanger

Abstract

dc:description.abstract

A test system for a hybrid cooled heat exchanger was designed, and the test facility was constructed based on ASHRAE Standard 41.2-1987. A conventional air-cooled tube-fin heat exchanger was tested with and without application of wetting water. The baseline tests were conducted to investigate the heat exchanger performance improvement by applying evaporative cooling technology. The heat exchanger capacity and air side pressure drop were measured while varying operating conditions and heat exchanger inclination angles. The results show the heat exchanger capacity increased by 170% with application of the hybrid cooling technology, but the air side pressure drop increased by 130%. Additional research investigating air fan power was also conducted, which increased 120% from the dry condition to the hybrid cooled condition. In summary, the potential for improving the heat exchanger performance by applying hybrid cooling is shown in this research.

Degree

thesis:*
Department dc:contributor.department
Mechanical Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2011

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Tsao, Han-Chuan
Advisor dc:contributor.advisor
  • Radermacher, Reinhard

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1903/12366

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Tsao, Han-Chuan. Experimental Study of Hybrid Cooled Heat Exchanger. Digital Repository at the University of Maryland, 2011. http://hdl.handle.net/1903/12366