Digital Repository at the University of Maryland
EFFECTS OF RADIANT HEAT FLUX ON CLEAN AGENT PERFORMANCE FOR CLASS-C STANDARDS
Abstract
dc:description.abstractThis thesis investigates the effects of radiant heat flux on clean agent extinguishing concentrations. This data is sought to support standards that address Class C hazards. Using the REED apparatus, performance of clean agents IG-100, IG-55, IG-541, HFC-125, HFC-227ea and FK-5-1-12 at heat flux levels of 0-40 kW/m2 was examined. It was found that clean agent extinguishing concentrations increased with an added heat flux. An alternate method of testing with the REED apparatus was also examined. Clean agents examined in the test were IG-100, IG-55, IG-541, HFC-125 and HFC-227ea at heat flux levels from 0-5 kW/m2. It was found that clean agent extinguishing concentrations increased by 33 to 45 percent from the original testing method. The new testing method was also found to be more repeatable and less time consuming.
Degree
thesis:*- Department dc:contributor.department
- Fire Protection Engineering
- Grantor dc:publisher
- Digital Repository at the University of Maryland
- Year dc:date.issued
- 2012
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Patel, Romil
- Advisor dc:contributor.advisor
-
- Milke, James
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1903/13573