Back to search

Digital Repository at the University of Maryland

VENTILATION IMPACT ON AIRBORNE TRANSMISSION OF RESPIRATORY ILLNESS IN STUDENT DORMITORIES

Abstract

dc:description.abstract

This work presents a study of the effect of ventilation rates on the bioaerosols that cause upper respiratory illness. A network of 147 sensors was placed in a pair of dormitories on a college campus to measure carbon dioxide concentrations over two semesters. The concentration results served as input into multi-zone ventilation models of the two buildings, which had different heating, ventilation, and air conditioning (HVAC) systems. The dormitory with a central mechanical ventilation system had, as expected, a higher turnover of fresh air compared to the other, which relied on exhaust fans and infiltration. This well-ventilated building also contained far fewer occupants with recorded upper respiratory illness incidence in comparison to the poorly ventilated building. The central ventilation system increased dorm room ventilation rates by 500%, while decreasing respiratory illness incidence by over 85%. Comparative studies have shown similar findings with increased ventilation reducing incidence of upper respiratory illness by an order of magnitude.

Degree

thesis:*
Department dc:contributor.department
Mechanical Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2018

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Jenkins, Sara T
Advisor dc:contributor.advisor
  • Srebric, Jelena

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Jenkins, Sara T. VENTILATION IMPACT ON AIRBORNE TRANSMISSION OF RESPIRATORY ILLNESS IN STUDENT DORMITORIES. Digital Repository at the University of Maryland, 2018. https://doi.org/10.13016/sadj-dny0