Back to search

Digital Repository at the University of Maryland

Feasibility Analysis and FDS Modeling of Water Mist Fire Suppression Systems for Protection of Aircraft Hangars

Abstract

dc:description.abstract

Concern about PFAS containing foam fire suppression agents’ negative environmental impact motivated the U.S. Air Force to perform a two-phase feasibility analysis of water mist systems for protection of aircraft hangars. Phase I involved a feasibility analysis of COTS water mist technologies based on manufacturer specifications, literature, and previous test data. Phase I identified seven manufacturers who have developed systems with potential for successful protection of aircraft hangars. Phase II used FDS to model two low pressure and one high pressure system identified in Phase I. Phase II completed an analysis and validation simulations of the Lagrangian particle, extinction, and evaporation model in FDS. Following validation simulations each nozzle was tested in a full-scale hangar configuration for protection of a JP-8 spill fire. The results found the high-pressure mist system was able to extinguish the fire and earlier activation times lead to less damage to the aircraft and hangar compartment.

Degree

thesis:*
Department dc:contributor.department
Fire Protection Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2021

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Steranka, Karolyn
Advisor dc:contributor.advisor
  • Milke, James

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Steranka, Karolyn. Feasibility Analysis and FDS Modeling of Water Mist Fire Suppression Systems for Protection of Aircraft Hangars. Digital Repository at the University of Maryland, 2021. https://doi.org/10.13016/ss9z-9atp