Digital Repository at the University of Maryland
An Assessment of the Use of Flame Retardant Plastics for Museum Applications
Abstract
dc:description.abstractHalogenated flame retardant plastic sheeting may help to reduce flame spread in museums; however, the plastics contain chemicals that may be harmful to museum objects in situ, particularly metals. This study assesses historical and contemporary problems and benefits associated with flame retardant plastics with respect to museum applications. This issue was addressed by pairing statistical data on museum fires with standard and novel methods for assessing corrosivity, while also creating a format for future assessments of fire-safety related practices as they are applied in museum settings. Flame retardant plastics were found to cause small rates of corrosion in copper, approximately 1.2 milli-inches per year (mpy), compared to pure polyethylene which corrodes at approximately 0.83 mpy. Conventional testing methods show that flame retardant plastics can be considered safe for limited museum use and that they delay ignition from small heat sources, but they must be assessed for each individual scenario.
Degree
thesis:*- Department dc:contributor.department
- Fire Protection Engineering
- Grantor dc:publisher
- Digital Repository at the University of Maryland
- Year dc:date.issued
- 2007
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Leikach, Danielle Caryn
- Advisors dc:contributor.advisor
-
- Mowrer, Frederick
- Brostoff, Lynn
Rights
- Language dc:language.iso
- en_US
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1903/7824