Back to search

Digital Repository at the University of Maryland

Stream-wise Discharge Characteristics of Pendant Sprinkler Sprays

Abstract

dc:description.abstract

Detailed atomization measurements in actual sprinklers are needed for proper spray specification in suppression modeling and analysis. In basic pendant sprinkler configurations, the spray originates from two streams corresponding to flow deflected along the tines of the pendant and flow passing through the void spaces between the tines. In this study, measurements of flow splits (between space and tine streams), sheet breakup distances, drop size, and drop velocity measurements were performed over a range of sprinkler geometries and injection pressures to characterize the near-field sprinkler spray. These detailed measurements were used to support the development of scaling laws describing the effects of injector geometry and injection conditions on sprinkler discharge characteristics.

Degree

thesis:*
Department dc:contributor.department
Fire Protection Engineering
Grantor dc:publisher
Digital Repository at the University of Maryland
Year dc:date.issued
2009

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Do, Chi Tran
Advisor dc:contributor.advisor
  • Marshall, André W

Rights

Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1903/9498

Chain of custody

source
Harvested from
University of Maryland
Base URL
api.drum.lib.umd.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Do, Chi Tran. Stream-wise Discharge Characteristics of Pendant Sprinkler Sprays. Digital Repository at the University of Maryland, 2009. http://hdl.handle.net/1903/9498