Back to search

University of Missouri--Columbia

Fuse holder damage investigation

Abstract

dc:description.abstract

The explosion of fuse holders at a certain 161 kV: 34.5 kV Ameren UE substation in the Potosi area was investigated. The Alternative Transients Program -Electromagnetic Transients Program (ATP-EMTP) was used to model and simulate the electrical behavior of transient overcurrents and overvoltages created by switching events in an effort to identify the cause of damage to a certain fuse holder used to protect the 4.5 MVAR capacitor bank on the 34.5 kV side of the transformer. Simulation results indicated that switching can increase the peak of the transient overcurrent from the normal current operation by up to9.33 p.u. Thus, the switching phenomenon may play a role in fuse holder damage.

Degree

thesis:*
Name thesis:degree_name
M.S.
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Electrical and computer engineering (MU)
Grantor dc:publisher
University of Missouri--Columbia
Year dc:date.issued
2006

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Wacharasindhu, Tongtawee
Advisor dc:contributor.advisor
  • O'Connell, Robert M., 1949-

Subjects

dc:subject × 5

Rights

Language dc:language.iso
eng, English

Identifiers

dc:identifier.*
OCLC
166384398
Dc Identifier Bibid
b5945295x

Chain of custody

source
Harvested from
University of Missouri
Base URL
mospace.umsystem.edu/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Wacharasindhu, Tongtawee. Fuse holder damage investigation. Masters thesis, University of Missouri--Columbia, 2006. https://hdl.handle.net/10355/4599