Back to search

Michigan Technological University

Real time adaptive relay settings for Microgrid protection verified using Hardware in Loop

Abstract

dc:description.abstract

Microgrids with penetration of renewables is imposing new challenges for system protection. Renewables are characterized with high source impedance which limit the short circuit current. The value of short-circuit current is limited due to converters used which limit the current to a maximum of 1.1 to 1.5 times maximum rated load current. This can result in faults during the islanded mode of microgrid to go unnoticed if the relay settings are not adapted to account for it. The presence of such uncleared faults in the microgrid can result in exposing it to overcurrent for a long time which can damage the equipment. One solution is to have different protection element pickup settings for different modes of operation. This report discusses the development of an algorithm to switch these settings upon microgrid state changes and test the algorithm using OPAL-RT hardware in loop real-time testing with SEL-351S relay as the hardware.

Degree

thesis:*
Name thesis:degree_name
Master of Science in Electrical Engineering (MS)
Level thesis:degree_level
Open Access Master's Report
Discipline thesis:degree_discipline
Department of Electrical and Computer Engineering

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Harnekar, Aadam
Committee members dc:contributor.committeemember
  • Glen E. Archer
  • Leonard J. Bohmann
Contributors dc:contributor
  • Bruce A. Mork

Subjects

dc:subject × 6

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
Michigan Technological University
Base URL
digitalcommons.mtu.edu/do/oai/
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Harnekar, Aadam. Real time adaptive relay settings for Microgrid protection verified using Hardware in Loop. Open Access Master's Report thesis, https://doi.org/10.37099/mtu.dc.etdr/1228