Abstract
dc:description.abstract<p>Stability and response of automatically controlled liquid level systems was investigated theoretically by transient and frequency response analysis and experimentally on a laboratory liquid level system.</p><p>Transfer functions were derived for each component and were used to describe the response of the experimental system. The effect of measurement time constants on system performance was experimentally investigated. Poor control, but not instability, resulted from an increase in measurement time constant. The behavior of the system at various operating loads was determined experimentally. The system was unstable at the maximum measureable flow rate, but stable at all other loads. Theoretical response curves did not show an unstable system at the maximum inlet flow rate, but did show cycling above 70% of the maximum inlet flow rate. This tendency towards cycling and control valve characteristics caused the system to become unstable.</p><p>The investigation showed that it is necessary to carefully match system load and control valve operating characteristics to insure good control of commercial installations.</p>
Degree
thesis:*- Name thesis:degree_name
- Master of Science in Chemical Engineering - (M.S.)
- Discipline thesis:degree_discipline
- Chemical Engineering
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Rosen, Milton Kalman
- Contributors dc:contributor
-
- Herbert Dengler
- Jerome J. Salamone
- Joseph Joffe
Subjects
dc:subject × 2Identifiers
dc:identifier.*- Repository record dc:identifier
- https://digitalcommons.njit.edu/theses/3240