Back to search

NJIT

The quasisteady approach for thermal analysis of frost action below refrigerated warehouses

Abstract

dc:description.abstract

<p>The quasisteady method of analysis has been used to determine the frost depth below refrigerated warehouses. For the case when the ground temperature is different from phase change temperature, the solution is obtained by numerical integration of the equation governing the phase change process. When the ground temperature approaches the phase change temperature closed form solution is obtained. The results obtained from the quasisteady method compare well with the experimental results. The results presented in this thesis should find use in the design of the refrigerated warehouses in the colder regions of the world.</p>

Degree

thesis:*
Name thesis:degree_name
Master of Science in Mechanical Engineering - (M.S.)
Discipline thesis:degree_discipline
Mechanical Engineering

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Bag, Milan Kumar
Contributors dc:contributor
  • P. Hrycak
  • John Vincent Droughton
  • Robert P. Kirchner

Subjects

dc:subject × 5

Identifiers

dc:identifier.*
Repository record dc:identifier
https://digitalcommons.njit.edu/theses/3499

Chain of custody

source
Harvested from
NJIT
Base URL
digitalcommons.njit.edu/do/oai/
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Bag, Milan Kumar. The quasisteady approach for thermal analysis of frost action below refrigerated warehouses. https://digitalcommons.njit.edu/theses/3499