Back to search

Monterey, California. Naval Postgraduate School

An experimental investigation of the effect of condensate inundation on heat transfer in a horizontal tube bundle.

Abstract

dc:description.abstract

A test facility to evaluate the effect of condensate inundation on heat transfer within a horizontal tube bundle was designed, constructed and validated. Five 15.9 mm (5/8 in.) nominal outside diameter, smooth stainless steel tubes were utilized in a vertical row. They were located in an equilateral triangular array with a spacing to diameter ratio of 1.5. Heat transfer performance was determined for each tube in the bundle. Data was taken by condensing steam at about 21 kPa (3 psia) on the outside of each tube. Each tube was cooled by water on the inside at velocities of 0.78 to 7.0 m/sec (2.56 to 23 ft/sec). The overall heat transfer coefficient was determined directly from experimental data. The inside and outside heat transfer coefficients were determined using the Wilson plot technique. Observation of condensate flow showed lateral droplet motion along the tube in portions of the condenser as well as side drainage, particularly over the first three tubes. Outside heat transfer coefficients were lower than expected when compared to Nusselt theory, possibly due to the effects of secondary vapor flow and/or non-condensable gases. Recommendations to improve validation are provided.

Degree

thesis:*
Name thesis:degree_name
M.S. in Mechanical Engineering
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Mechanical Engineering
Department dc:contributor.department
Mechanical Engineering
Grantor dc:publisher
Monterey, California. Naval Postgraduate School
Year dc:date.issued
1980

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Eshleman, Donald Eugene
Advisor dc:contributor.advisor
  • Marto, P.J.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • This publication is a work of the U.S. Government as defined in Title 17, United States Code, Section 101. Copyright protection is not available for this work in the United States.
  • Approved for public release; distribution is unlimited.

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10945/17587

Chain of custody

source
Harvested from
Naval Postgraduate School
Base URL
calhoun.nps.edu/server/oai/request
Last updated
2026-11-20
Source record
OAI-PMH GetRecord
citation

Eshleman, Donald Eugene. An experimental investigation of the effect of condensate inundation on heat transfer in a horizontal tube bundle.. Masters thesis, Monterey, California. Naval Postgraduate School, 1980. https://hdl.handle.net/10945/17587