Naval Postgraduate School
Nucleate pool-boiling of R-114 refrigerant and oil mixtures from water-heated enhanced surfaces
Abstract
dc:description.abstractHeat- transfer measurements were made for a single, water-heated tube in a pool of R-114 to simulate operating conditions of a water chiller. Data were obtained for a smooth copper tube, and for two commercially available tubes: a spirally roped copper-nickel tube with a porous coating; and a copper tube with a structured outer surface and a multiple-start helical ridged inner surface. Measurements were made for refrigerant-oil mixtures at oil concentrations from 0 to 6 mass percent with a boiling pool temperature of 13.8 ˚C. Results for the two enhanced tubes with and without oil are compared to the smooth tube data. Enhancement factors for the overall heat- transfer coefficient were 4.0 and 3.6 for the structured surface and porous-coated tubes, respectively, in pure refrigerant and at a water Velocity of 2 m/s. For these same conditions the enhancement factors for the outside heat- transfer coefficient were 14.6 and 6.4 for the porous-coated and structured surface tubes, respectively.
Degree
thesis:*- Name thesis:degree_name
- M.S. in Mechanical Engineering
- Level thesis:degree_level
- Masters
- Discipline thesis:degree_discipline
- Mechanical Engineering
- Department dc:contributor.department
- Mechanical Engineering
- Grantor
- Naval Postgraduate School
- Year dc:date.issued
- 1986
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- McManus, Stephen M.
- Advisors dc:contributor.advisor
-
- Marto, P.J.
- Wanniarachchi, A.S.
Subjects
dc:subject × 1Rights
dc:rights- Statement dc:rights
-
- This publication is a work of the U.S. Government as defined in Title 17, United States Code, Section 101. Copyright protection is not available for this work in the United States.
- Approved for public release; distribution is unlimited.
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- https://hdl.handle.net/10945/22004