Back to search

Monterey, California. Naval Postgraduate School

An advanced study of natural convection immersion cooling of 3 x 3 array of simulated components in an enclosure filled with dielectric liquid

Abstract

dc:description.abstract

An experimental study has been conducted to examine the three dimensional natural convection heat transfer from an array of simulated electronic components immersed in a chamber filled with Fluorinert FC-75, a commercially available dielectric liquid. The top and bottom walls of the chamber were maintained at uniform temperature while all other surfaces were insulated. The simulated components were in the form of a 3 x 3 array of discrete protruding aluminum blocks, each with geometrical dimensions of a 20 Pin Dual-inline-Package. The components were electrically powered resulting in a range of energy dissipation levels from 0.1 to 3.1 watts. Flow visualization in steady state was accomplished using Magnesium particles illuminated by a Helium Neon laser plane. Component surface temperature measurements allowed determination of the heat transfer characteristics. Timewise fluctuations of temperature at several locations were measured with increasing power levels. Keywords: Computer programs, Electronic cooling, Protruding heat sources, Flow visualization, Convective heat transfer, Immersion cooling, Dielectric liquids, Theses. (jhd)

Degree

thesis:*
Name thesis:degree_name
M.S. in Engineering Science
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Engineering Science
Grantor dc:publisher
Monterey, California. Naval Postgraduate School
Year dc:date.issued
1988

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Benedict, Terry J.
Advisors dc:contributor.advisor
  • Kelleher, Matthew Dennis
  • Joshi, Yogendra

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • This publication is a work of the U.S. Government as defined in Title 17, United States Code, Section 101. Copyright protection is not available for this work in the United States.
  • Approved for public release; distribution is unlimited.

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10945/22860

Chain of custody

source
Harvested from
Naval Postgraduate School
Base URL
calhoun.nps.edu/server/oai/request
Last updated
2026-11-20
Source record
OAI-PMH GetRecord
citation

Benedict, Terry J.. An advanced study of natural convection immersion cooling of 3 x 3 array of simulated components in an enclosure filled with dielectric liquid. Masters thesis, Monterey, California. Naval Postgraduate School, 1988. https://hdl.handle.net/10945/22860