Back to search

Monterey, CA; Naval Postgraduate School

Natural convection immersion cooling of an array of heated protrusions in an enclosure filled with dielectric liquid: effects of enclosure width and fluid Prandtl number

Abstract

dc:description.abstract

An experimental investigation of natural convection immersion cooling of an array (3 by 3 horizontally-placed heated discrete protrusions) in an enclosure filled with dielectric fluids has been conducted. Each rectangular protrusion simulates a 20 pin dual-inline-package. Effects of enclosure width and fluid Prandl number were examined. Five different spacings from 42 mm to 7 mm and two dielectric fluids, FC-75 (PR=25 at 27(o) C) and FC-43 (Pr=82 at 27(o)C).were used. The top boundary of the enclosure was kept constant at 10(o)C and the bottom boundary was insulated during the experiments. Power dissipation levels per component ranged from 0.115 W to 2.9 w. Component surface temperature measurements were used to obtain the nondimensional heat transfer parameters. In the case of FC-75 and 30 and 7 mm spacings, and in the case of FC-43 and 7 mm spacing, timewise fluctuations of temperature at steady state in several locations were recorded with increasing power level.

Degree

thesis:*
Name thesis:degree_name
M.S. in Mechanical Engineering
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Mechanical Engineering
Department dc:contributor.department
Mechanical Engineering
Grantor dc:publisher
Monterey, CA; Naval Postgraduate School
Year dc:date.issued
1991

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Aytar, Erol
Advisor dc:contributor.advisor
  • Kelleher, Matthew D.

Rights

dc:rights
Statement dc:rights
  • Copyright is reserved by the copyright owner.
  • Approved for public release; distribution is unlimited.

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10945/28387

Chain of custody

source
Harvested from
Naval Postgraduate School
Base URL
calhoun.nps.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Aytar, Erol. Natural convection immersion cooling of an array of heated protrusions in an enclosure filled with dielectric liquid: effects of enclosure width and fluid Prandtl number. Masters thesis, Monterey, CA; Naval Postgraduate School, 1991. https://hdl.handle.net/10945/28387