University of Akron
Feedback Control for Maximizing Combustion Efficiency of a Combustion Burner System
Abstract
dc:descriptionAn observer-controller pair was designed to regulate the fuel flow rate and the flue-gas oxygen ratio of a combustion boiler. The structure of the observer was a proportional-integral state estimator. The designed controller was composed of a combination of two common controller structures: state-feedback with reference tracking and proportional-integral-derivative(PID).A discrete-time, linear state-space model of the combustion system was developed such that the linear controller and observer could be designed. This required establishing separate models pertaining to the combustion process, actuators, and sensors. The complete model of the combustion system incorporated all three models. The combustion model, which related the flue-gas oxygen ratio to the fuel and oxygen flow rates, was obtained using the mathematical formulas corresponding to combustion of natural gas. The actuators were modeled using measured fuel and oxygen flow rate data for various actuator signals, and fitting the data to a parametric model. The established nonlinear models for the combustion process and actuators required linearization about a specified operating point. The sensors model was then obtained using the predictive error identification technique based on batch input-output data.For the acquired model of the combustion system, a linear quadratic regulator was used to calculate the optimal state feedback gain. The classical controller gains were determined by tuning the gains and evaluating the simulation of the closed-loop response. Computer-aided simulations provided evidence that the controller and state estimator could regulate the desired set point in the presence of moderate disturbances. The observer-controller pair was implemented and verified on an experimental boiler system by means of an embedded system. Even in the presence of a disturbance resulting from a 50% blockage of the surface area of the air intake duct, the closed-loop system was capable of regulating the desired set point for slow-varying reference signal changes.
Degree
thesis:*- Name thesis:degree_name
- Master of Science in Engineering
- Level thesis:degree_level
- masters
- Discipline thesis:degree_discipline
- Electrical Engineering
- Grantor dc:publisher
- University of Akron
- Year dc:date
- 2016
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Horning, Marcus
- Contributors dc:contributor
-
- Ida, Nathan
Subjects
dc:subject × 10Rights
dc:rights- Statement dc:rights
-
- unrestricted
- This thesis or dissertation is protected by copyright: all rights reserved. It may not be copied or redistributed beyond the terms of applicable copyright laws.
- Language dc:language
- English
Identifiers
dc:identifier.*- Repository record dc:identifier
- http://rave.ohiolink.edu/etdc/view?acc_num=akron1459356183