Back to search

University of Akron

A System for the Non-Intrusive Detection of Damage in Underground Power Cables: Damage Modeling and Sensor System Design

Abstract

dc:description

A system for non-intrusive sensing of underground power cable impedance is presented. The impedance sensor is used for the detection of damage to underground power cables. The system is capable of taking measurements without the need to interrupt power service. To isolate the impedance measurement from the effects of customer loading, a blocking unit is proposed which presents an open circuit to the impedance sensor in the transmission line at the point where the blocker is clamped onto the cable. Both of the proposed devices are prototyped and evaluated. The impedance sensor is demonstrated to be capable of accurate impedance measurements within a 2% error over a range from 50 to 1000 Ohms. The blocker is demonstrated to provide approximately 30 dB of attenuation over the designed ranged of measurement frequencies. The system can detect impedance changes resulting from corrosion or damage in underground power cables.

Degree

thesis:*
Name thesis:degree_name
Master of Science in Engineering
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
Electrical Engineering
Grantor dc:publisher
University of Akron
Year dc:date
2016

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Granger, Matthew G.
Advisor dc:contributor.advisor
  • Veillette, Robert

Subjects

dc:subject × 10

Rights

dc:rights
Statement dc:rights
  • unrestricted
  • This thesis or dissertation is protected by copyright: all rights reserved. It may not be copied or redistributed beyond the terms of applicable copyright laws.
Language dc:language
English

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
OhioLINK
Base URL
etd.ohiolink.edu/acprod/odb_etd/ws/oai/oai
Last updated
2026-11-27
Source record
OAI-PMH GetRecord
citation

Granger, Matthew G.. A System for the Non-Intrusive Detection of Damage in Underground Power Cables: Damage Modeling and Sensor System Design. masters thesis, University of Akron, 2016. http://rave.ohiolink.edu/etdc/view?acc_num=akron1470838336