FIELD INVESTIGATION OF OPERATIONAL PARAMETERS LEADING TO THEPREMATURE FAILURE OF PRECAST CONCRETE STRUCTURES BYMICROBIALLY-INDUCED CONCRETE CORROSION.
Abstract
dc:descriptionThe Lorain County Rural Wastewater District (LORCO) Phase 1 system, installedas a result of failing privately owner residential septic systems circa 2012, was a $34million dollar infrastructure investment to meet Ohio Environmental Protection Agency(OEPA) requirements and facilitate economic growth in rural Lorain County.Certain sections of the collection system and a wastewater pump station began to showsevere signs of internal concrete deteriorating in non-tidal regions due to sulfuric acidsecreted by various microorganisms that colonized on exposed moist concrete surfaceswithin the high humidity enclosed sewer environment. The deterioration process, knownas Microbial Induced Concrete Corrosion (MICC) profoundly reduced the service life ofinfrastructure from 100+ years to as little as 5-10 years. The primary focus of this fieldstudy was to identify what mechanisms and system parameters were responsible for rapiddeterioration of the precast concrete structures.System maintenance policies, procedures, wastewater strength, non-residential use,development of biofilm, variation of hydrogen sulfide gas generation based on season,time-of-day and system geometrics were also studied. The failing sewer sections, headspace parameters such as hydrogen sulfide gas, relative humidity, temperature weremeasured over an extended period. Wastewater stream properties, via grab samples, weretaken of dissolved oxygen (DO), temperature, pH and mVORP, sulfate, carbonaceousBOD, COD, sulfur, TSS, VSS and VA. Wastewater stream was found to be anaerobic.ivMeasured values from the pump station wet well found BOD5 = 2300 mg/L, COD=714mg/L, VSS=960 mg/L, TSS=1000 mg/L, pH=5.6, mVORP = -286 mV. Stream propertieswithin the long force main and wet well were conducive to hydrogen sulfide formation.During this study, [H2S]g varied over time and season, headspace humidity averaged 95-99%, and internal temperature also remained constant over the 24-hour sampling period.Transition manholes were found to be the major generator of hydrogen sulfide gas atpoints of force main discharge points. Based upon extensive hydrogen sulfide gasmonitoring, the study established a strong correlation between [H2S]g and concretecorrosion. Gas pulse peak [H2S]g values of 257 ppmv (max), 159.6 +/- 39 ppmv wereobserved. No records, procedures/policies were found in operations on force main and/orpump station (O&M) related to biofilm, hydrogen sulfide mitigation, chemical dosing orend-of-line flushing of force mains. The very long force main lengths betweenstructures, slow progression of residential connections allowed for very long hydraulicretention times (HRT) that facilitated development of microorganisms in non-tidal areas,biofilm on internal pipe surfaces. A lack of knowledge and preventative maintenancetraining of operation staff played a major key factor in the premature failure of theinfrastructure.
Degree
thesis:*- Name thesis:degree_name
- Master of Science
- Level thesis:degree_level
- masters
- Discipline thesis:degree_discipline
- Civil Engineering
- Grantor dc:publisher
- University of Akron
- Year dc:date
- 2025
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- GAYDAR, JACK RICHARD
- Advisor dc:contributor.advisor
-
- Miller, Christopher
- Chair dc:contributor.committeechair
-
- Roke, David
Subjects
dc:subject × 7Rights
dc:rights- Statement dc:rights
-
- unrestricted
- This thesis or dissertation is protected by copyright: all rights reserved. It may not be copied or redistributed beyond the terms of applicable copyright laws.
- Language dc:language
- English
Identifiers
dc:identifier.*- Repository record dc:identifier
- http://rave.ohiolink.edu/etdc/view?acc_num=akron1762933545429583