Case Western Reserve University School of Graduate Studies

Data-driven EDIFES Analysis for Heating Type of Commercial Buildings: Validation of EDIFES’s Electricity Disaggregation Strategy

Abstract

dc:description

In this study, we improved the virtual classification of buildings’ heating types by incorporating knowledge of how buildings actually behave and diversifying the types of models used to describe the building’s heating type. The heating type of a building is determined by whether it uses electricity for heating, cooling, neither, or both. The break point temperature represents the temperature that the heating or cooling system switches on, is critical for the categorization of the heating type. The new method described herein improved the accuracy of heating type classification by 4.7% and the accuracy of break point calculation by 9.1% on a data set of 301 manually reviewed buildings. We statistically compared the proportion of buildings identified with each heating type to the proportion of buildings with each heating type present in a large reference government data set with sub-metered electricity consumption data. The results of two chi-square tests of independence resulted in p-values that were much smaller than the significance level of 0.05, indicating that the distribution of proportions between the samples did not match. However, when a two-proportion z-test was run comparing only the most common category in both data sets, the p-value was found to be 0.791, which indicates that the proportion of non-electric heating and electric cooling buildings identified matches the reference data set. Similarly, the heating and cooling electrical load calculated by the EDIFES virtual energy audit software were compared by heating type classification to the government data set usingWilcoxon ranked sumtests. The resulting p-values were 0.677, 0.524, and 0.064 for the three most common heating type classifications. This finding means that when the heating type is identified as one of these categories by the EDIFES software, the electricity consumption identified is comparable to physical sub-metering. Additionally, this study explored the possibility of using electricity data with a 60-minute interval instead of the standard 15-minute interval. Results were compared after both data sets are run through the EDIFES software. The adjusted r-squared for the comparison between the plug load hourly and 15-minute results is 0.66 for plug load disaggregation and 0.792 for heating and cooling load identification with minimal filtering applied.

Degree

thesis:*
Name thesis:degree_name
Master of Engineering
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
EMC - Mechanical Engineering
Grantor dc:publisher
Case Western Reserve University School of Graduate Studies
Year dc:date
2022

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • West, Alexander
Chairs dc:contributor.committeechair
  • French, Roger
  • Yuan, Chris

Subjects

dc:subject × 5

Rights

dc:rights
Statement dc:rights
  • unrestricted
  • This thesis or dissertation is protected by copyright: all rights reserved. It may not be copied or redistributed beyond the terms of applicable copyright laws.
Language dc:language
English

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
OhioLINK
Base URL
etd.ohiolink.edu/acprod/odb_etd/ws/oai/oai
Last updated
2026-11-27
Source record
OAI-PMH GetRecord
citation

West, Alexander. Data-driven EDIFES Analysis for Heating Type of Commercial Buildings: Validation of EDIFES’s Electricity Disaggregation Strategy. masters thesis, Case Western Reserve University School of Graduate Studies, 2022. http://rave.ohiolink.edu/etdc/view?acc_num=case1639060987524804