COORDINATING LIQUID AND FREE AIR COOLING WITH WORKLOAD ALLOCATION FOR DATA CENTER POWER MINIMIZATION

Abstract

dc:description

Data centers are seeking more efficient cooling techniques to reduce their operating expenses, because cooling can account for 30-40\% of the power consumption of a data center. Recently, liquid cooling has emerged as a promising alternative to traditional air cooling, because it can help eliminate undesired air recirculation. Another emerging technology is free air cooling, which saves chiller power by utilizing outside cold air for cooling. Some existing data centers have already started to adopt both liquid and free air cooling techniques for significantly improved cooling efficiency and more data centers are expected to follow. In this thesis, we propose SmartCool, a power optimization scheme that effectively coordinates different cooling techniques and dynamically manages workload allocation for jointly optimized cooling and server power. In sharp contrast to the existing work that addresses different cooling techniques in an isolated manner, SmartCool systematically formulates the integration of different cooling systems as a constrained optimization problem. Furthermore, since geo-distributed data centers have different ambient temperatures, SmartCool dynamically dispatches the incoming requests among a network of data centers with heterogeneous cooling systems to best leverage the high efficiency of free cooling. A light-weight heuristic algorithm is proposed to achieve a near-optimal solution with a low runtime overhead. We evaluate SmartCool both in simulation and on a hardware testbed. The results show that SmartCool outperforms two state-of-the-art baselines by having a 38\% more power savings.

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Grantor dc:publisher
The Ohio State University
Year dc:date
2014

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Li , Li
Advisor dc:contributor.advisor
  • Wang, Xiaorui

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • unrestricted
  • This thesis or dissertation is protected by copyright: all rights reserved. It may not be copied or redistributed beyond the terms of applicable copyright laws.
Language dc:language
English

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
OhioLINK
Base URL
etd.ohiolink.edu/acprod/odb_etd/ws/oai/oai
Last updated
2026-11-27
Source record
OAI-PMH GetRecord
citation

Li , Li. COORDINATING LIQUID AND FREE AIR COOLING WITH WORKLOAD ALLOCATION FOR DATA CENTER POWER MINIMIZATION. masters thesis, The Ohio State University, 2014. http://rave.ohiolink.edu/etdc/view?acc_num=osu1395743682