Back to search

Oklahoma State University

Experimental Facility to Measure Fouling Resistance in Condensers

Abstract

dc:description.abstract

Heat exchangers are employed to transfer thermal energy between two fluids. Fouling is defined as the accumulation of deposits on the heat transfer surface which provides a resistance to the heat transfer, thereby decreasing the heat transfer capacity of the surface. The air conditioning industry has been under pressure to improve the efficiency of systems adopting these heat exchangers. The current thesis involves the design and construction of an experimental facility to measure the thermal and hydraulic performances of three brazed plate heat exchangers (BPHEs) of different geometries (chevron angles and aspect ratios) operating under controlled fouling conditions. Fouling tests conducted on the three BPHEs revealed that the chevron angle of the plates had a significant impact on the overall heat transfer coefficient (UA) and fouling resistance, a BPHE with a chevron angle of 300 had a UA 0.75 times less and a fouling resistance 15 times larger than a BPHE with a chevron angle of 630 and identical aspect ratio. The aspect ratio was found to have a slight impact on the UA and fouling resistance, a BPHE with an aspect ratio 4.1 had a UA 2 % greater and a fouling resistance 17 % lower than a BPHE with an aspect ratio of 2.1 and identical chevron angle.

Degree

thesis:*
Department dc:contributor.department
Mechanical & Aerospace Engineering
College dc:contributor.school
Engineering, Architecture, and Technology
Grantor dc:publisher
Oklahoma State University
Year dc:date.issued
2010

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Ramesh, Annamalai
Advisor dc:contributor.advisor
  • Cremaschi, Lorenzo
Committee members dc:contributor.committeemember
  • Spitler, Jeffery
  • Morton, Jeremy

Rights

dc:rights.accessrights
Statement dc:rights.accessrights
  • Open Access
  • Copyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
Language dc:language
en_US

Identifiers

dc:identifier.*
Mods Identifier Filename
Ramesh_okstate_0664M_11079.pdf

Chain of custody

source
Harvested from
Oklahoma State University
Base URL
openresearch.okstate.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
related terms
citation

Ramesh, Annamalai. Experimental Facility to Measure Fouling Resistance in Condensers. Oklahoma State University, 2010. https://hdl.handle.net/20.500.14446/10041