Back to search

Oklahoma State University

Modeling Packaged Heat Pumps in a Quasi-steady State Energy Simulation Program

Abstract

dc:description.abstract

The purpose of this study is to validate steady-state heat pump models implemented in EnergyPlus. The heat pump models include air-to-air, water-to-air heat and water-to-water. Part load models are used to adjust the models' full load outputs to part load conditions. New curve-fit heat pump models are proposed and compared to existing parameter estimation based models using experimental data. Uncertainties in the models are analyzed and quantified. A short study is also conducted on the compressor shell heat loss that is often neglected by the manufacturer. The EnergyPlus heat pump models agree with experimental data with an error of less than 12%. Most of the errors are attributed to the discrepancies between the catalog and the experimental measurement. The curve-fit models in EnergyPlus agree with detailed and parameter estimation based models within 6%. Curve-fit heat pump models also allow extrapolation beyond the catalog data without catastrophic error and require less computation time and are more robust than parameter estimation based models. The current drawback of curve-fit models is the inability to simulate the degradation effect of antifreeze on water source heat pump performance. The heat pump component models in EnergyPlus have been validated but the control algorithm and system interactions still require further validation with measured data.

Degree

thesis:*
Department dc:contributor.department
Mechanical & Aerospace Engineering
College dc:contributor.school
Engineering, Architecture, and Technology
Grantor dc:publisher
Oklahoma State University
Year dc:date.issued
2005

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Tang, Chih Chien

Rights

dc:rights.accessrights
Statement dc:rights.accessrights
  • Open Access
  • Copyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
Language dc:language
en_US

Identifiers

dc:identifier.*
Mods Identifier Filename
Tang_okstate_0664M_1318.pdf

Chain of custody

source
Harvested from
Oklahoma State University
Base URL
openresearch.okstate.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
related terms
citation

Tang, Chih Chien. Modeling Packaged Heat Pumps in a Quasi-steady State Energy Simulation Program. Oklahoma State University, 2005. https://hdl.handle.net/20.500.14446/10075