Back to search

Oklahoma State University

Measurement of Thermal Conductivity of Pipe Insulation Systems at below Ambient Temperature and in Wet Condensing Conditions with Moisture Ingress

Abstract

dc:description.abstract

When pipes are used for chilled water, glycol brines, refrigerants, and other chilled fluids, energy must be spent to compensate for heat gains through the wall of the pipes. Higher fluid temperature at the point of use decreases the efficiency of the end-use heat exchangers and increases the parasitic energy consumption. Mechanical pipe insulation systems are often used to limit the heat gains and save energy in commercial buildings. Pipe insulation systems play an important role for the health of the occupied space. When a chilled pipe is uninsulated or inadequately insulated, condensation might occur and water will drip onto other building surfaces possibly causing mold growth. The critical issue with cold pipes is that the temperature difference between the pipe and its surrounding ambient air drives water vapor in to the insulation system and condensation commonly occurs when the water vapor comes in contact with the chilled pipe surface. This thesis experimentally studies this issue for pipe insulation systems operating at below ambient temperature. The moisture content and the associated thermal conductivity of several pipe insulation systems were measured at various wet condensing conditions with moisture ingress. Accelerated type tests in laboratory showed the propensity of moisture accumulation in several insulation systems due to the cylindrical configuration, split joints, and micro-imperfections in the jacketing system. The data in the present work showed that the thermal conductivity increased systematically when water vapor entered the pipe insulation system.

Degree

thesis:*
Department dc:contributor.department
Mechanical & Aerospace Engineering
Grantor dc:publisher
Oklahoma State University
Year dc:date.issued
2015

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Zhu, Weiwei
Advisor dc:contributor.advisor
  • Cremaschi, Lorenzo
Committee members dc:contributor.committeemember
  • Ghajar, Afshin
  • Sallam, Khaled

Rights

dc:rights.accessrights
Statement dc:rights.accessrights
  • Open Access
  • Copyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
Language dc:language
en_US

Identifiers

dc:identifier.*
Mods Identifier Filename
Zhu_okstate_0664M_13760.pdf

Chain of custody

source
Harvested from
Oklahoma State University
Base URL
openresearch.okstate.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
related terms
citation

Zhu, Weiwei. Measurement of Thermal Conductivity of Pipe Insulation Systems at below Ambient Temperature and in Wet Condensing Conditions with Moisture Ingress. Oklahoma State University, 2015. https://hdl.handle.net/20.500.14446/33467