Back to search

Oklahoma State University

Development and Analysis of Model Based Economizer Strategies

Abstract

dc:description.abstract

Two new model based economizer strategies were developed and implemented in the EnergyPlus simulation program. Model performance was verified by comparing EnergyPlus results with previously developed models. Results agreed within 25%. Both detailed and bypass coil models were evaluated for potential use in the model based economizer strategies. Energy and peak load analyses were performed for three benchmark buildings using five economizer strategies for 15 US climatic conditions. The impact of sensor errors on energy savings and coil design was also discussed. For office type buildings, it was found that model based economizer strategies do have energy savings potential as long as sensors are well maintained. However, if sensors are poorly maintained, differential dry bulb was found to be the best strategy. For Hospitals and Hotels with high minimum outside air requirements due to high occupancy, the economizer strategies resulted in lower energy savings. The bypass coil model was found to be in agreement with results obtained for detailed coil model based strategies. Using different simulation methods to size the cooling coil can change the coil size by up to 100%. Accounting for sensor error in simulation based coil design, tends to decrease the difference between the design day and annual peak cooling coil loads. Based on the results of the study, it was recommended that simulation capabilities should be modified to account for user specified sensor errors and ASHRAE standards should be modified to characterize economizer use based on building use and qualities of sensors.

Degree

thesis:*
Department dc:contributor.department
Mechanical & Aerospace Engineering
College dc:contributor.school
Engineering, Architecture, and Technology
Grantor dc:publisher
Oklahoma State University
Year dc:date.issued
2009

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Bhansali, Amit
Advisor dc:contributor.advisor
  • Fisher, Daniel E.
Committee members dc:contributor.committeemember
  • Spitler, Jeffrey
  • Cremaschi, Lorenzo

Rights

dc:rights.accessrights
Statement dc:rights.accessrights
  • Open Access
  • Copyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
Language dc:language
en_US

Identifiers

dc:identifier.*
Mods Identifier Filename
Bhansali_okstate_0664M_10545.pdf

Chain of custody

source
Harvested from
Oklahoma State University
Base URL
openresearch.okstate.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
related terms
citation

Bhansali, Amit. Development and Analysis of Model Based Economizer Strategies. Oklahoma State University, 2009. https://hdl.handle.net/20.500.14446/9898