Back to search

Oklahoma State University

Design of an Experimental Facility for Frost Growth Study in Microchannel Heat Exchangers

Abstract

dc:description.abstract

This report focused on the new experimental methodology developed to investigate the frost and defrost thermal hydraulic performances of louvered folded fin microchannel heat exchangers under initial frost cycle, defrost cycle, and subsequent re-frost cycles. The required laboratory conditions are 35/33 &degF dry-/wet-bulb temperature, with the air velocity around 100 ~ 300 fpm. In the air side, the required conditions were reached by a humidification, a cooling and a re-heating process with a fan, a refrigeration coil, a humidifier and a re-heating coil. In the refrigerant side, the required inlet coolant temperature was controlled by an automatically controlled heater and a plate heat exchanger connected with the chiller. The frost accumulation was measured by a precision scale for frost weight, and a videoscope for frost thickness. Uncertainties on U and hout were investigated based on both precision and bias uncertainties.

Degree

thesis:*
Department dc:contributor.department
Mechanical & Aerospace Engineering
College dc:contributor.school
Engineering, Architecture, and Technology
Grantor dc:publisher
Oklahoma State University
Year dc:date.issued
2009

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Cai, Shanshan
Advisor dc:contributor.advisor
  • Cremaschi, Lorenzo
Committee members dc:contributor.committeemember
  • Spitler, Jeffrey D.
  • Fisher, Daniel E.

Rights

dc:rights.accessrights
Statement dc:rights.accessrights
  • Open Access
  • Copyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
Language dc:language
en_US

Identifiers

dc:identifier.*
Mods Identifier Filename
CAI_okstate_0664M_10508.pdf

Chain of custody

source
Harvested from
Oklahoma State University
Base URL
openresearch.okstate.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
related terms
citation

Cai, Shanshan. Design of an Experimental Facility for Frost Growth Study in Microchannel Heat Exchangers. Oklahoma State University, 2009. https://hdl.handle.net/20.500.14446/9906