Back to search

University of Saskatchewan

COMPUTERIZED GENERATOR DIFFERENTIAL PROTECTION

Abstract

dc:description.abstract

This thesis presents a computerized scheme which detects the presence of phase to ground and phase to phase stator faults on power system generators. The fault/no-fault decisions are based on the amplitude ratio of the "fault" and "average-through" currents from a selected generator phase. Techniques for fast amplitude extraction from sampled inputs are evaluated. The proposed protection scheme is amenable to a time-shared digital computer approach. An analog input data pre-processor, used to reduce the sampling requirements of the digitizer, is described. An input data monitor is included to activate the more sophisticated software only when required. Fast acting software is included to restrict subsequent calculations to the data from the faulted phase. Special attention is directed towards making valid amplitude comparisons during the transient period immediately, following fault incidence. A data logging function, which retains and returns information from any conditions analyzed by the software, is included to permit reconstruction of the pre-fault and post-fault currents. The operation of the hardware and software is also reported. The results of extensive tests, performed on single and three phase versions, were used to evaluate the performance of the scheme. Approximately 800 case studies including internal and external faults using a three phase generator, are presented. This research was financed by a National Research Council bursary and grant No. A7249.

Degree

thesis:*
Name thesis:degree_name
Master of Science (M.Sc.)
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Electrical Engineering
Department thesis:degree_department
Electrical and Computer Engineering
Grantor
University of Saskatchewan
Year dc:date.issued
1972

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Wind, David W.

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10388/11841

Chain of custody

source
Harvested from
University of Saskatchewan
Base URL
harvest.usask.ca/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Wind, David W.. COMPUTERIZED GENERATOR DIFFERENTIAL PROTECTION. Masters thesis, University of Saskatchewan, 1972. https://hdl.handle.net/10388/11841