Comparison of the Performance of the H.M. Briggs Library's Cooling System with Manufacturer's Rated Performance and a Common Mathematical Model

Abstract

dc:description.abstract

The objective of this study was to monitor and record cooling equipment performance in the H.M. Briggs Library for the 1998 cooling season. The measured data was used to calculate key performance parameters for the aforementioned cooling systems. The measured performance was then compared to manufacturer's rated performance values and that of a mathematical model. The following were concluded regarding the comparison of the measured performance vs. manufacturer's rated performance values and the mathematical model. Measured vs. Manufacturer's Performance 1. At 85°F and 46°F leaving condenser and leaving chilled water temperatures, respectively, the Briggs Library chiller appeared to perform worse than manufacturer's data. Further, the Briggs Library chiller appeared to perform slightly better than manufacturer's rated performance values as the load increased. 2. At 85°F and 48°F leaving condenser and leaving chilled water, respectively, the Briggs Library chiller appeared to perform worse than manufacturer's data. 3. At 87.5°F and 46°F leaving condenser and leaving chilled water, respectively, the Briggs Library chiller appeared to perform better than manufacturer's performance data. Further, the measured performance appeared better than the manufacturer's performance as the load increased. Measured vs. Mathematical Model 1. At 85°F and 46°F leaving condenser and leaving chilled water, respectively, the mathematical model overestimated power consumption at given loads. 2. At 85°F and 48°F leaving condenser and leaving chilled water, respectively, the Briggs Library chiller compared well with the mathematical model. Further, it appeared that the mathematical model tended to slightly underestimate power consumption at given loads. 3. At 87.5°F and 46°F leaving condenser and leaving chilled water, respectively, the Briggs Library chiller differed with the mathematical model. The computer model tended to overestimate power consumption at given loads. Effect of Leaving Condenser and Leaving Evaporator Water Temperature 1. A quadratic model is appropriate in describing the relationship of power vs. load. 2. Changing the leaving chilled water temperature given a leaving condenser water temperature did have a significant effect on power consumption. 3. Changing the leaving condenser water temperature given a leaving chilled water temperature did not have a significant effect on power consumption.

Degree

thesis:*
Name thesis:degree_name
Master of Science (MS)
Level thesis:degree_level
Thesis - University Access Only
Discipline thesis:degree_discipline
Mechanical Engineering

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Hengeveld, Derek W.

Identifiers

dc:identifier.*
Repository record dc:identifier
https://openprairie.sdstate.edu/etd/6054

Chain of custody

source
Harvested from
South Dakota State University
Base URL
openprairie.sdstate.edu/do/oai/
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Hengeveld, Derek W.. Comparison of the Performance of the H.M. Briggs Library's Cooling System with Manufacturer's Rated Performance and a Common Mathematical Model. Thesis - University Access Only thesis, https://openprairie.sdstate.edu/etd/6054