South Dakota State University
Effect of Backfill Type on Horizontal Heat Exchanger Performance for Ground Source Heat Pump Systems
Abstract
dc:description.abstractHeat exchanger configurations and backfills for Ground Source Heat Pump (GSHP) systems were surveyed and a representative group was chosen which included three heat exchanger geometries, three backfills and two backfill configurations. Three types of analyses, including steadystate, constant boundary condition transient, and pulsed boundary condition transient heat transfer from the pipes to the surrounding soil were performed using the finite element program ANSYS. The possibility of using insulation as a means to reduce thermal interaction and increase heat transfer rates was examined. The results of these models were compared by heat transfer rate per foot of trench and foot-of pipe, soil thermal resistance for the selected pipe geometries, and approximate cost per ton of cooling. Employing insulation proved ineffective. Utilizing higher thermal conductivity backfill resulted in higher heat transfer rates. No model proved better than the basic model on the basis of installation cost.
Degree
thesis:*- Name thesis:degree_name
- Master of Science (MS)
- Level thesis:degree_level
- Thesis - University Access Only
- Discipline thesis:degree_discipline
- Mechanical Engineering
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Coyle, Kathleen R.
- Contributors dc:contributor
-
- Charles Remund
Subjects
dc:subject × 2Rights
dc:rights- Language dc:language
- English
Identifiers
dc:identifier.*- Repository record dc:identifier
- https://openprairie.sdstate.edu/etd2/88