Back to search

University of Southampton

An investigation into partial discharge activity within three-phase belted cables

Abstract

dc:description.abstract

Industrially driven interest in the field of partial discharge (PD) diagnostics has rapidly increased in recent years. Utilities are turning to continuous asset monitoring methods to inform them on the real-time health of plant. The majority of London's medium voltage (MV) distribution network is constructed from paper insulated lead covered (PILC) belted cables. The vast majority of this cable was commissioned in the 60's and 70's and is now nearing the end of its design life. PD diagnostics have been proposed as a possible tool for the condition monitoring of these distribution cables. Little is known about the characteristics of the PD activity that is produced as cables of this design degrade under rated conditions.<br/><br/>This thesis describes the development of a PD measurement experiment that records PD data from either defective or damaged three-phase MV PILC cables under rated voltage conditions. The experiment has been designed to replicate the environment experienced by cable circuits in the field. The aim was to investigate the potential transfer of knowledge generated by the experiment onto an on-line commercial operational system. An investigation into the PD produced by the various degradation mechanisms have been undertaken to evaluate the relationship between the PD source conditions and recorded signals.<br/><br/>It has been found that the phase-resolved PD patterns produced by different degradation mechanisms are unique. Consequently, a PD source discrimination technique has been successfully applied to both experiment and field data. The algorithm relies on the finding that the wavelet energy (WE) distribution of a PD pulse is source dependent. A support vector machine (SVM) was used to accurately classify PD pulses from different sources that had been tested experimentally. The ability to accurately discriminate between different PD sources in both experiment and field data should lead to a significant step forward in the field of PD diagnostics.

Degree

thesis:*
Name dc:type.qualificationname
Ph.D.
Level dc:type.qualificationlevel
doctoral
Grantor dc:publisher.institution
University of Southampton
Year dc:date.issued
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Hunter, J.A.
Advisor dc:contributor.advisor
  • Lewin, P.L.
ORCID person:identifier.orcid

Rights

Language dc:language.dcterms_iso639_2
eng

Chain of custody

source
Harvested from
University of Southampton
Base URL
eprints.soton.ac.uk/cgi/oai2
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Hunter, J.A.. An investigation into partial discharge activity within three-phase belted cables. doctoral thesis, University of Southampton, 2013.