Back to search

University of Strathclyde

Voltage-based backup protection and protection performance analysis using wide-area PMU data

Abstract

dc:description.abstract

This dissertation describes a system that analyses and summarises the operation of protection and provides backup protection functionality, using only voltage data from PMUs and wide-area communications infrastructure. The ability to rapidly identify the presence of faults, their locations and the presence of protection/circuit breaker failures, solely from voltage measurements, is the overarching contribution from this work. The scheme can operate in addition to existing backup schemes to provide a further, or alternative, relatively inexpensive, effective, simple, fast, wide-area backup protection to improve the resilience of power systems. Methods of power system model simplification for different types of fault have also been developed for establishing the capabilities and voltage thresholds of the scheme, and this simplification method is also claimed as a contribution arising from the work. It is shown how the system can operate for a wide range of fault levels, types and resistances { thereby addressing one of the key challenges for protection associated with concerns over protection in the context of reducing and more variable fault levels in future power systems.To validate the developed scheme, case studies assessing scheme performance in several scenarios are presented. Variations of fault resistance, time of fault occurrence, fault location, and fault levels are simulated in Matlab (Simscape Power Systems) using the well-established and accepted IEEE 14-bus network.Hardware in the loop tests are also conducted using an RTDS and actual PMU devices to test and validate the performance of the scheme and to demonstrate its ability to operate using actual hardware and in real time. Applicability of the developed system to large-scale power networks is also demonstrated. It is shown that the scheme is suited to interconnected power systems, and can operate with both reduced fault levels and for different types of faults with high resistances.Future work and suggestions for extensions to the developed system are also presented.

Degree

thesis:*
Name dc:type.qualificationname
phd
Level dc:type.qualificationlevel
doctoral-pg
Grantor dc:publisher.institution
University of Strathclyde
Year dc:date.issued
2019

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Yu, Fangzhu
Advisors dc:contributor.advisor
  • Booth, Campbell
  • Dyśko, Adam
Author Identifier dc:creator.authoridentifier
  • 201569503

Rights

Identifiers

dc:identifier.*
Identifier
T15253

Chain of custody

source
Harvested from
University of Strathclyde
Base URL
stax.strath.ac.uk/catalog/oai
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Yu, Fangzhu. Voltage-based backup protection and protection performance analysis using wide-area PMU data. doctoral-pg thesis, University of Strathclyde, 2019. https://stax.strath.ac.uk/concern/theses/707957774