Back to search

The University of Texas at Austin

Ozone interactions with HVAC filters

Abstract

dc:description.abstract

Experiments were conducted in a laboratory to investigate ozone interactions with HVAC filters. Experimental results indicate that activated carbon filters can effectively remove ozone, used commercial HVAC filters remove more ozone than used residential HVAC filters, and for most filters the ozone removal efficiency declined rapidly and converged to a non-zero steady-state value. Experimental results also indicate that repeated exposure of residential and commercial filters to ozone following a 24-hour period of no exposure led to a regeneration of ozone removal efficiency. Experimental results suggest that filter material, manufacturer, particle loading, operation time and operation location affect ozone removal on HVAC filters. A plug flow reactor model was developed to investigate the ozone removal process and a time scale analysis was used to analyze the fundamental processes involved with ozone reactions on filters. The steady-state ozone removal efficiency on HVAC filters is speculated to be limited by either ozone or reactant diffusion inside particles, and regeneration is due to internal diffusion of reactive species to sites available to ozone for reaction. Experiments were also conducted in a laboratory to evaluate ozone removal on small filters loaded with either diesel or oleic acid particles. Filters loaded with oleic acid vi had one to two orders of magnitude less particle surface area but greater ozone removal capacity than filters loaded with diesel particles. Ozone removal capacity was observed to be proportional to the mass of oleic acid particles on filters. The results presented in this study should facilitate future studies related to ozone chemistry in HVAC systems, and may ultimately lead to the design of filters that effectively reduce the exposure of building occupants to ozone.

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
Doctoral
Discipline thesis:degree_discipline
Civil Engineering
Department thesis:degree_department
Civil, Architectural, and Environmental Engineering
Grantor
The University of Texas at Austin
Year dc:date.issued
2006

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Zhao, Ping
Advisor dc:contributor.advisor
  • Siegel, Jeffrey A.,Corsi, Richard L.,

Subjects

dc:subject × 4

Rights

dc:rights
Statement dc:rights
  • Copyright is held by the author. Presentation of this material on the Libraries' web site by University Libraries, The University of Texas at Austin was made possible under a limited license grant from the author who has retained all copyrights in the works.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
OCLC
166290552
Identifier
b6865523x

Chain of custody

source
Harvested from
University of Texas
Base URL
repositories.lib.utexas.edu/server/oai/request
Last updated
2026-11-20
Source record
OAI-PMH GetRecord
citation

Zhao, Ping. Ozone interactions with HVAC filters. Doctoral thesis, The University of Texas at Austin, 2006. https://hdl.handle.net/2152/2965