Back to search

University of Toronto

Distance Protection of Systems with Inverter-based Resources

Abstract

dc:description.abstract

This dissertation focuses on the challenges faced by distance relays and their supervising elements, including directional, phase-selection, and loss-of-voltage (LOV) elements, in the systems with inverter-based resources (IBRs). A comprehensive dual current control scheme is proposed for IBRs during the low-voltage ride-through (LVRT) mode to address the challenges. This method addresses the shortcomings of existing solutions and enables correct operation of distance, directional, and phase-selection elements during all types of faults. The proposed method controls the IBR to operate as a voltage source behind a virtual impedance in the positive-sequence circuit and a single inductive virtual impedance in the negative-sequence circuit, thereby emulating the phase angles of an SG's fault current. The proposed method also maximizes the active and reactive current generation of the IBR during faults and emulates the relative incremental sequence current magnitudes of an SG. It is unveiled, for the first time, in this dissertation that IBRs can jeopardize the security of the LOV detection element, which is another supervising element for distance relays. A new LOV detection method is proposed to address this problem. The proposed solution centers around the fault current signature of IBRs and performs superior to the existing LOV detection elements. This method operates reliably regardless of the type of generation units in the system and is sufficiently fast to prevent relay misoperation during LOV conditions. The impact of different implementations of distance element on protection of systems with IBRs is also investigated in this dissertation. The focus is on the relays implemented using the phase comparators and the reactance method. It is unveiled, for the first time, that the ground and phase elements of a distance relay that uses these methods are prone to under-/over-reach in the systems with IBRs. A detailed analysis on the root causes of the problems as well as the measures to alleviate them is provided. Besides, it is shown that IBRs can adversely impact the operation of not only the distance relay that protects their tie-line but also the relays of the neighboring lines. The above studies are all supported by hardware-in-the-loop testing of commercial relays.

Degree

thesis:*
Department dc:contributor.department
Electrical and Computer Engineering
Year dc:date.issued
2022

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Banaiemoqadamfariman, Amin
Advisors dc:contributor.advisor
  • Hooshyar, Ali
  • Iravani, Reza

Subjects

dc:subject × 6

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/1807/128355

Chain of custody

source
Harvested from
University of Toronto
Base URL
utoronto.scholaris.ca/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Banaiemoqadamfariman, Amin. Distance Protection of Systems with Inverter-based Resources. 2022. https://hdl.handle.net/1807/128355