University of British Columbia
Local assessment of transient stability for generator tripping
Abstract
dc:descriptionThe local variables of a synchronous generator are investigated as possible indicators of the transient stability of the generator. A number of case studies are carried out on three test systems to find out which generator variable or variables can be used. By comparing the conventional swing curve of each generator with its local acceleration curve during the same transient period, a new criterion for transient stability assessment is developed to replace existing generator tripping schemes that rely upon pre-determined contingency studies. The new criterion is based upon the behavior of the acceleration of the generator following a disturbance to the system. No measurements from any other machine in the system are required to assess the stability of the generator.
Degree
thesis:*- Name thesis:degree_name
- Master of Applied Science - MASc
- Level thesis:degree_level
- master's
- Discipline thesis:degree_discipline
- Electrical and Computer Engineering
- Grantor dc:publisher
- University of British Columbia
- Year dc:date
- 1984
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Mihirig, Ali Mohamed
Rights
dc:rights- Statement dc:rights
-
- For non-commercial purposes only, such as research, private study and education. Additional conditions apply, see Terms of Use https://open.library.ubc.ca/terms_of_use.
- Language dc:language
- eng
Identifiers
dc:identifier.*- Handle dc:identifier
- http://hdl.handle.net/2429/24945