Measurement of power system subsynchronous impedances and comparison with computer simulations

Abstract

dc:description

A test method is developed to measure the equivalent (driving point) positive sequence impedance, as a function of frequency, of an operating power system. The technique used is to apply a phase-to-phase fault at the system node of interest and record the transient voltage across and current in the fault. These quantities are then transformed into the frequency domain. The system driving point impedance is then taken as the ratio of the fault voltage to the current at each point in the frequency domain. Field results from a phase-to-phase fault at a central location on the B.C. Hydro 500 k-V network are presented and analysed to determine the system driving point impedance. The measured impedance versus frequency characteristic is compared with a predicted impedance characteristic based on an Electro-Magnetic Transient program study of a detailed model of the major B.C. Hydro transmission and generation. Correlation between the measured and calculated impedance is good, with explanations offered for any localized significant disagreement. The explanations offered are subsequently verified by Ontario Hydro's improvements to the analysis of the test data and additions to the computer model data.

Degree

thesis:*
Name thesis:degree_name
Master of Applied Science - MASc
Level thesis:degree_level
master's
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Grantor dc:publisher
University of British Columbia
Year dc:date
1984

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Hughes, Michael Brent

Rights

dc:rights
Statement dc:rights
  • For non-commercial purposes only, such as research, private study and education. Additional conditions apply, see Terms of Use https://open.library.ubc.ca/terms_of_use.
Language dc:language
eng

Identifiers

dc:identifier.*
Handle dc:identifier
http://hdl.handle.net/2429/25071

Chain of custody

source
Harvested from
University of British Columbia
Base URL
circle.library.ubc.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Hughes, Michael Brent. Measurement of power system subsynchronous impedances and comparison with computer simulations. master's thesis, University of British Columbia, 1984. http://hdl.handle.net/2429/25071