dc:description

This thesis presents a method of detecting electrical islands in low voltage distributed generator networks by measuring negative sequence impedance differences between islanded and utility connections. Extensive testing was conducted on a commercial building and 25 kV distributed generator fed network by measuring naturally occurring and artificially injected negative sequence components. Similarly, this technique was tested using the IEEE 399-1990 bus test case using the EMTP software. The practical measurements have been matched to simulations where further system performance characteristics of detecting power system islands has been successfully demonstrated. Measured results indicate that unbalanced load conditions are naturally occurring and readily measurable while deliberately unbalanced loads can increase the accuracy of negative sequence impedance islanding detection. The typically low negative sequence impedance of induction motors was found to have only a small effect in low voltage busses, though large machines can effect the threshold settings. Careful placement of the island detector is required in these situations. The negative sequence impedance measurement method is an improvement on previous impedance measurement techniques for islanding detection due to its accuracy, and distinctly large threshold window which have challenged previous impedance based islanding detection techniques.

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy - PhD
Level thesis:degree_level
doctoral
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Grantor dc:publisher
University of British Columbia
Year dc:date
2008

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Wrinch, Michael C.

Rights

dc:rights
Statement dc:rights
  • Attribution-NonCommercial-NoDerivatives 4.0 International
Language dc:language
eng

Identifiers

dc:identifier.*
Handle dc:identifier
http://hdl.handle.net/2429/3418

Chain of custody

source
Harvested from
University of British Columbia
Base URL
circle.library.ubc.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Wrinch, Michael C.. Negative sequence impedance measurement for distributed generator islanding detection. doctoral thesis, University of British Columbia, 2008. http://hdl.handle.net/2429/3418