Back to search

University of British Columbia

Using refractive index to monitor oil quality in high voltage transformers

Abstract

dc:description

Insuring reliable operation of high voltage electrical equipment, such as transformers and cables, is of great importance to the power industry. This is done by monitoring the equipment. A large portion of this monitoring includes analyzing the quality of the insulating oils and observing various compounds formed in the oils during aging. Most often, transformer monitoring includes routine oil sampling and analysis, which has proven to be very effective at diagnosing faults and determining the insulation condition. Many techniques have been demonstrated for the purpose of online monitoring, and various commercial products are available. However, utility companies are still looking for more cost effective methods to monitor their equipment between sampling intervals. The work presented here was performed in order to investigate the use of refractive index for monitoring insulating oils. The refractive indices of various oil samples obtained from the field were measured and differences were observed. Accelerated aging experiments were conducted in a laboratory and increases in the refractive indices of these artificially aged oils were observed. Experiments were conducted to determine what by-products would contribute to this increased refractive index by investigating the effects of individual groups on the refractive index change. These groups included aromatic compounds, polar compounds, furans, acid, and fault gases. We observe that the formation of furans, acids, and fault gases cannot be detected using refractive index for the concentrations typically found in the field. We conclude that changes in the refractive index of an oil can be used as an indicator of the oil’s aging and its break down and the formation of aromatic and polar compounds.

Degree

thesis:*
Name thesis:degree_name
Master of Applied Science - MASc
Level thesis:degree_level
master's
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Grantor dc:publisher
University of British Columbia
Year dc:date
2008

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Kisch, Ryan John

Rights

dc:rights
Statement dc:rights
  • Attribution-NonCommercial-NoDerivatives 4.0 International
Language dc:language
eng

Identifiers

dc:identifier.*
Handle dc:identifier
http://hdl.handle.net/2429/5636

Chain of custody

source
Harvested from
University of British Columbia
Base URL
circle.library.ubc.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Kisch, Ryan John. Using refractive index to monitor oil quality in high voltage transformers. master's thesis, University of British Columbia, 2008. http://hdl.handle.net/2429/5636