Bayesian inference of parameters in power system dynamic model using trajectory sensitivities
Abstract
dc:descriptionWe propose an analytically tractable Bayesian method to infer parameters in power system dynamic models from noisy measurements of bus-voltage magnitudes and frequencies as well as active- and reactive-power injections. The proposed method is computationally appealing as it bypasses the large number of system model simulations typically required in sampling-based Bayesian inference. Instead, it relies on analytical linearization of the nonlinear system differential-algebraic-equation model enabled by trajectory sensitivities. Central to the proposed method is the construction of a linearized model with the maximum probability of being (closest to) the actual nonlinear model that gave rise to the measurement data. The linear model together with Gaussian prior leads to a conjugate family where the parameter posterior, model evidence, and their gradients can be computed in closed form, markedly improving scalability for large-scale power systems. We illustrate the effectiveness and key features of the proposed method with numerical case studies for a 3-bus system. Algorithmic scalability is then demonstrated via case studies involving the New England 39-bus test system.
Degree
thesis:*- Name thesis:degree_name
- Master of Applied Science - MASc
- Level thesis:degree_level
- master's
- Discipline thesis:degree_discipline
- Electrical and Computer Engineering
- Grantor dc:publisher
- University of British Columbia
- Year dc:date
- 2021
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Nagi, Rubinderjit Singh
Rights
dc:rights- Statement dc:rights
-
- Attribution-NonCommercial-NoDerivatives 4.0 International
- Language dc:language
- eng
Identifiers
dc:identifier.*- Handle dc:identifier
- http://hdl.handle.net/2429/77565