Back to search

University of Nevada - Reno

An Investigation Into: I) Active Flow Control for Cold-Start Performance Enhancement of a Pump-Assisted, Capillary-Driven, Two-Phase Cooling Loop II) Surface Tension of n-Pentanol + Water, a Self-Rewetting Working Fluid, from 25 °C to 85 °C

Abstract

dc:description.abstract

Cold-start performance enhancement of a pump-assisted, capillary-driven, two-phase cooling loop was attained using proportional integral and fuzzy logic controls to manage the boiling condition inside the evaporator. The surface tension of aqueous solutions of n-Pentanol, a self-rewetting fluid, was also investigated for enhancing heat transfer performance of capillary driven (passive) thermal devices was also studied. A proportional-integral control algorithm was used to regulate the boiling condition (from pool boiling to thin-film boiling) and backpressure in the evaporator during cold-start and low heat input conditions. Active flow control improved the thermal resistance at low heat inputs by 50% compared to the baseline (constant flow rate) case, while realizing a total pumping power savings of 56%. Temperature overshoot at start-up was mitigated combining fuzzy-logic with a proportional-integral controller. A constant evaporator surface temperature of 60°C with a variation of ±8°C during start-up was attained with evaporator thermal resistances as low as 0.10 cm2_K/W. The surface tension of aqueous solutions of n-Pentanol, a self-rewetting working fluid, as a function of concentration and temperature were also investigated. Self-rewetting working fluids are promising in two-phase heat transfer applications because they have the ability to passively drive additional working fluid towards the heated surface; thereby increasing the dryout limitations of the thermal device. Very little data is available in literature regarding the surface tension of these fluids due to the complexity involved in fluid handling, heating, and experimentation. Careful experiments were performed to investigate the surface tension of n-Pentanol + water. The concentration and temperature range investigated were from 0.25%wt. to1.8%wt and 25°C to 85°C, respectively.

Degree

thesis:*
Level thesis:degree_level
Master's Degree
Department thesis:degree_department
Mechanical Engineering
Year dc:date.issued
2014

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Bejarano, Roberto V.
Advisor dc:contributor.advisor
  • Park, Chanwoo
Committee members dc:contributor.committeemember
  • Fu, Henry
  • Chandra, Dhanesh

Subjects

dc:subject × 6

Rights

dc:rights
Statement dc:rights
  • In Copyright(All Rights Reserved)
  • Author(s)

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/11714/2975

Chain of custody

source
Harvested from
University of Nevada - Reno
Base URL
scholarwolf.unr.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Bejarano, Roberto V.. An Investigation Into: I) Active Flow Control for Cold-Start Performance Enhancement of a Pump-Assisted, Capillary-Driven, Two-Phase Cooling Loop II) Surface Tension of n-Pentanol + Water, a Self-Rewetting Working Fluid, from 25 °C to 85 °C. Master's Degree thesis, 2014. http://hdl.handle.net/11714/2975