Back to search

University of South Florida

Analysis Of The Impact Of The Location Of A Window Type Air-Conditioner On Thermal Comfort In An Office Room

Abstract

dc:description

This study considers airflow simulations to evaluate the impact of different window air-conditioner locations on the thermal comfort in an office room (OR). This thesis compares the air distribution for an office room by using computational fluid dynamics (CFD) modeling to previously studied rooms. The air distribution was modeled on a typical office room window air conditioning unit, air supply from a high pressure on the top and the low pressure exhaust on the bottom considering the existing manufacturing ratios for surface areas. The discharge angle for the supply grill of the AC unit was varied from 20 to 40 degrees. The position of the air conditioner was also varied and studied at 60%, 75% and 90% of the total height of the room. In addition, the location of the occupant within the office room was varied, two locations were studied, one where the occupant is far from the unit and the other to closer to the AC unit at the middle of the room. Predictions of the air movement, room temperature, room relative humidity, comfort level, and distribution of contaminants within the office room are shown. Analysis of these simulations is discussed. Energy estimations are also performed and evaluated. The positions of the air-conditioner unit, the inlet angle and the occupant position in the office room have shown to have an important impact on supply controlling air quality and thermal comfort. Results are in good agreements with the experimental data. The primary function of a HVAC (heating refrigerating and air conditioning) system is the generation and maintenance of comfort for occupants in a conditioned space [1]. This work also provides a detailed analysis of three-dimensional mixed convective flow induced by a window air conditioning system. Using a three dimensional CFD simulation, several characteristics of human comfort are analyzed. The results of this study show a strong relation between the position of the wall-mounted air conditioning unit and the thermal comfort of the occupant. The results are in good agreement with the experimental data and the two dimensional simulation.

Degree

thesis:*
Level thesis:degree_level
Thesis
Discipline thesis:degree_discipline
Mechanical Engineering
Grantor
University of South Florida
Year dc:date
2005

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Begdouri, Hamza
Contributors dc:contributor
  • Muhammad Rahman, Ph.D.
  • Autar Kaw, Ph.D.
  • Frank Pyrtle, III, Ph.D.

Subjects

dc:subject × 7

Rights

Language dc:language
EN-US

Identifiers

dc:identifier.*
Repository record dc:identifier
https://digitalcommons.usf.edu/etd/2780

Chain of custody

source
Harvested from
University of South Florida
Base URL
digitalcommons.usf.edu/do/oai/
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Begdouri, Hamza. Analysis Of The Impact Of The Location Of A Window Type Air-Conditioner On Thermal Comfort In An Office Room. Thesis thesis, University of South Florida, 2005. https://digitalcommons.usf.edu/etd/2780