Hosted by Utah State University Libraries
Cavitation Limits and the Effect of Aeration on Cone Valves
Abstract
dc:description.abstractCavitation in cone valves can cause eventual valve failure. However, little data are available on cavitation limits for solid plug cone valves. Flow conditions were identified for a 6 inch cone valve where incipient, critical, incipient damage, and choking cavitation limits occurred at valve openings between 20 and 70 degrees. A description of how these limits are used to predict cavitation intensity is given. Air was used to reduce the damage levels. Aeration increased the allowable pressure drop for damage free operation 6 to 72 percent for valve openings less than 70 degrees. A chart is given for predicting when a cone valve will draw air. Location of the air injection point is not important as long as it is introduced into the separation zone.
Degree
thesis:*- Name thesis:degree_name
- Master of Science (MS)
- Level thesis:degree_level
- Thesis
- Discipline thesis:degree_discipline
- Civil and Environmental Engineering
- Grantor dc:publisher
- Hosted by Utah State University Libraries
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Mumford, Bart "L"
- Contributors dc:contributor
-
- J. Paul Tullis
- Roland Jeppson
- Reynold K. Watkins