Back to search

University of Leeds

Gas Explosions in, and Propagating from, Low Strength Enclosures

Abstract

dc:description.abstract

This research aimed to investigate the escalating effects of explosion propagation from electrical control boxes within lightweight steel-constructed buildings, focusing on elucidating the flame propagation mechanisms responsible for intensifying Vapour Cloud Explosion (VCE) severity, as observed in the Buncefield incident of 2005. The research aimed to determine if any escalating effects could be caused by the explosion propagating from the control box and the building into a larger cloud. A series of controlled explosion experiments were conducted using a 47 m3 vessel designed to mimic the structural properties of buildings like the Buncefield pumphouse, where it is believed the cloud was first ignited. Initially, experiments utilising 4.2% propane-air mixtures were carried out to understand baseline venting mechanisms and pressure development, with the vessel vent covered with steel panels and, for comparison, plastic sheeting. Findings indicate that lightweight steel panels hinging open during the initial stages of an explosion significantly enhance explosion severity due to their function as congestion elements. Subsequent experiments employed commercially available electrical control boxes to investigate the explosion propagation dynamics, resultant pressures, and flame speeds. Experiments were conducted without and with a flammable cloud of 8 m3 external to the control box contained in a tent. High-speed venting from the control box demonstrated a localised increase in flame speeds and overpressures, albeit the flame speeds attenuated considerably with a 0.35 m travel. However, congestion placed 0.5 m away from the vent without confinement didn’t result in increased flame speeds. The observed escalated explosion severity in lightweight steel buildings on high VCE hazard sites reveals a pressing concern regarding their structural failure mechanisms. Explosions originating from electrical control boxes showed an amplification of explosion severity, which only affected the immediate volume close to the box, suggesting that an obstruction-free zone of approximately 0.5 m from the control box could prevent an escalating explosion event. However, further studies are needed to thoroughly map the roles of confinement, immediate congestion, and high reactivity gases in such scenarios. Overall, this research significantly contributes to a better understanding of explosion propagation dynamics within industrially relevant and standard settings, thereby aiding in developing more robust safety measures and structural designs to mitigate the severity of VCEs.

Degree

thesis:*
Name dc:type.qualificationname
Ph.D
Level dc:type.qualificationlevel
doctoral
Grantor dc:publisher.institution
University of Leeds
Year dc:date.issued
2024

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Gill, Jason Peter
Advisors dc:contributor.advisor
  • Phylaktou, Herodotos
  • Andrews, Gordon
ORCID person:identifier.orcid

Rights

Language dc:language.dcterms_iso639_2
eng

Chain of custody

source
Harvested from
White Rose University Consortium
Base URL
etheses.whiterose.ac.uk/cgi/oai2
Last updated
2026-11-18
Source record
OAI-PMH GetRecord
related terms
citation

Gill, Jason Peter. Gas Explosions in, and Propagating from, Low Strength Enclosures. doctoral thesis, University of Leeds, 2024.