Spelling suggestions: "subject:"phasor 1ieasurement units"" "subject:"phasor 1ieasurement knits""
31 |
Estimação de estado harmônico para sistemas radiais de distribuição usando medição fasorial sincronizadaMelo, Igor Delgado de 18 September 2015 (has links)
Submitted by Renata Lopes (renatasil82@gmail.com) on 2015-12-16T11:21:48Z
No. of bitstreams: 1
igordelgadodemelo.pdf: 4931795 bytes, checksum: cf03c45f0f2492c6cf9186af1b3866a2 (MD5) / Approved for entry into archive by Adriana Oliveira (adriana.oliveira@ufjf.edu.br) on 2015-12-16T11:57:23Z (GMT) No. of bitstreams: 1
igordelgadodemelo.pdf: 4931795 bytes, checksum: cf03c45f0f2492c6cf9186af1b3866a2 (MD5) / Made available in DSpace on 2015-12-16T11:57:23Z (GMT). No. of bitstreams: 1
igordelgadodemelo.pdf: 4931795 bytes, checksum: cf03c45f0f2492c6cf9186af1b3866a2 (MD5)
Previous issue date: 2015-09-18 / Este trabalho objetiva apresentar uma metodologia capaz de estimar os componentes
harmônicos em sistemas de distribuição com topologia radial utilizando PMUs (Phasor
Measurement Units). Os estados a serem estimados serão as correntes passantes em todas
as linhas do sistema em coordenadas retangulares. Uma vez que essas correntes são obtidas,
torna-se possível o cálculo de outras grandezas elétricas através das equações de fluxo de
potência e leis de Kirchhoff. A metodologia considera poucas unidades de medição fasorial
(as PMUs) instaladas efetuando a leitura dos sinais de tensões nodais e correntes nas linhas
com distorção harmônica. A fim de restaurar a observabilidade do sistema por completo,
são considerados dados históricos de demanda de potência ativa/reativa, os quais serão
tratados como restrições de desigualdades excursionando entre um valor mínimo e máximo
considerados em um problema de otimização não linear que visa diminuir a diferença entre
os valores monitorados pelas PMUs e os calculados pela metodologia. As mencionadas
restrições permitem ao estimador o acompanhamento das variações sofridas ao longo
do tempo na curva de carga para a frequência fundamental e também para as demais
frequências. A abordagem proposta neste trabalho considera a modelagem trifásica de
equipamentos e linhas de distribuição, portanto, são modelados os efeitos de acoplamento
mútuo entre fases e a operação não linear de equipamentos de eletrônica de potência
tiristorizados. O método demonstra eficiência não apenas em estimar os componentes
harmônicos de um certo espectro considerado no estudo, como também se mostra uma
ferramenta prática de detecção e identificação de fontes harmônicas no sistema elétrico
de potência, além de explicitar um exemplo prático do uso de PMUs no que tange ao
monitoramento de redes de distribuição, carentes de acompanhamento em tempo real. A
metodologia ainda se mostra capaz de ser aliada a grandes estudos contextualizados em
qualidade de energia, uma vez que permite a estimação de índices de distorção harmônica. / This work aims to present a methodology which is capable of estimating harmonic components
for distribution systems with radial topology, using PMUs (Phasor Measurement
Units). The estimated states will be all branch currents of the system expressed in
rectangular coordinates. Once these currents are obtained, it is possible to calculate other
electrical quantities using power flow equations and also Kirchhoff’s law. The methodology
considers the installation of a few number of phasor measurement units which will measure
voltage and branch currents signals distorted by harmonic sources. In order to make the
whole system observable, historical data of active/reactive power demand will be treated
as inequality constraints varying between minimum and maximum limits described in
a non linear optimization problem, which aims to minimize the difference between the
values monitored by PMUs and the ones calculated by the methodology. The already
mentioned constraints allows the accompaniment of the variations occured in a typical load
curve during a period of time for the fundamental frequency and also for their multiples,
allowing the accompaniment of the harmonic load curve, normally unknown. The proposed
approach considers a three-phase modelling of equipments and distribution lines, subject
to their mutual coupling effects caused by mutual impedances between the lines. It will
also be considered electronic-based devices using thyristors located along the distribution
feeder, injecting harmonic currents in the system. The method demonstrates efficiency in
estimating the harmonic states of the net and also in detecting and identifying harmonic
sources in an eletric power system, besides showing a practical use of PMUs for the
monitoring of distribution systems, lacking in information and real-time accompaniment.
The method also enables the estimation of power quality indicators such as total harmonic
distortion.
|
32 |
Uma nova metodologia para estimação de estados em sistemas de distribuição radiais utilizando PMUsAlves, Guilherme de Oliveira 18 September 2015 (has links)
Submitted by Renata Lopes (renatasil82@gmail.com) on 2016-05-16T17:51:25Z
No. of bitstreams: 1
guilhermedeoliveiraalves.pdf: 1293169 bytes, checksum: a76074780b2af177b66be7c6435b16d1 (MD5) / Approved for entry into archive by Adriana Oliveira (adriana.oliveira@ufjf.edu.br) on 2016-06-28T12:25:31Z (GMT) No. of bitstreams: 1
guilhermedeoliveiraalves.pdf: 1293169 bytes, checksum: a76074780b2af177b66be7c6435b16d1 (MD5) / Made available in DSpace on 2016-06-28T12:25:31Z (GMT). No. of bitstreams: 1
guilhermedeoliveiraalves.pdf: 1293169 bytes, checksum: a76074780b2af177b66be7c6435b16d1 (MD5)
Previous issue date: 2015-09-18 / CAPES - Coordenação de Aperfeiçoamento de Pessoal de Nível Superior / O presente trabalho tem por objetivo apresentar uma nova metodologia para estimação
estática de estados em sistemas de distribuição de energia elétrica que estima as correntes
nos ramos como variáveis de estado utilizando medições de tensão e corrente de ramo
fasoriais oriundas de unidades de medição fasorial (Phasor Measurement Units - PMUs).
A metodologia consiste em resolver um problema de otimização não linear minimizando
uma função objetivo quadrática associada com as medições e estados estimados sujeito
às restrições de carga das barras da rede que não apresentam PMUs instaladas baseadas
em dados históricos, sendo esta a principal contribuição deste trabalho. Uma proposta
de alocação de PMUs também é apresentada e que consiste em alocar duas unidades
em cada ramificação do sistema, uma no começo e outra no final do trecho, procurando
utilizar o menor número possível e que não comprometa a qualidade dos estados estimados.
A resolução do problema de otimização é realizada de duas formas, através da ‘toolbox
fmincon’ do software Matlab, que é uma ferramenta muito utilizada na resolução de
problemas de otimização, e através da implementação computacional do Método de Pontos
Interiores com Barreira de Segurança (Safety Barrier Interior Point Method - SFTB - IPM)
proposto na literatura utilizada. Durante o processo de estimação de estados são utilizadas
medidas obtidas através de um fluxo de potência que simulam as PMUs instaladas nos
sistemas analisados variando o carregamento de cada sistema em torno da sua média
histórica de carga até atingir os limites superior e inferior estabelecidos, sendo verificado
o comportamento do estimador de estados perante a ocorrência de ruídos brancos nas
medidas de todos os sistemas analisados. Foram analisados um sistema de distribuição
tutorial de 15 barras e três sistemas encontrados na literatura contendo 33, 50 e 70 barras
respectivamente. No sistema tutorial e no de 70 barras foram incluídas unidades de
geração distribuída para se verificar o comportamento do estimador de estados. Todos
os resultados do processo de estimação de estados são obtidos com os dois métodos de
resolução apresentados e são comparados o desempenho de cada método, principalmente
em relação ao tempo computacional. Todos os resultados obtidos foram validados usando
um programa de fluxo de potência convencional e apresentam boa precisão com valor de
função objetivo baixo mesmo na presença de ruídos nas medidas refletindo de maneira
confiável o real estado do sistema de distribuição, o que torna a metodologia proposta
atraente. / This work aims at presenting a new methodology for static state estimation in electric
power distribution systems which estimates the branch currents as state variables using
voltage measurements and current phasor branch obtained from phasor measurement
units (Phasor Measurement Units - PMUs). The methodology consists of solving a
nonlinear optimization problem minimizing a quadratic objective function associated with
the estimated measurements and states, subject to load constraints for the non monitored
loads based on historical data, which is the main contribution of this work. A PMU
allocation strategy is presented which consists of allocating two PMUs for each system
branch, one at the beginning and another at the end, trying to use as little PMUs as
possible in such a way that the quality of the estimated states are not compromised. The
solution of the optimization problem is obtained through two ways, the first is the toolbox
‘fmincon’ from Matlab solver software which is a widely used tool in the optimization
problem. The second is a computer implementation of interior point method with security
barrier (SFTB - IPM) proposed in the literature. Comparisons of computing times and
results obtained with both methods are shown. A power flow program is used to obtain the
voltages and branch currents in order to emulate the PMUs data in the state estimation
process. Additionaly the non monitored loads are varied from the minimum bounds to
their maximum, allowing white noise errors from the PMUs measurements. A tutorial
test system of 15 buses is fully explored and three IEEE test systems of 33, 50 and 70
buses are used to show the effectiveness of the proposed methodology. For the tutorial
and 70 bus systems, distribued generation units were included to see the state estimator
behavior. All results from the state estimation process are obtained considering the
two presented solving methods and the computing times performance compared. The
results obtained were validated using a conventional power flow program and have good
accuracy with low objective function value even in the presence of white noise errors in
the measurements reflecting the reliability of the proposed methodology, making it very
attractive for distribution system monitoring.
|
33 |
Estimação de estados em sistemas de distribuição: uma abordadgem trifásica e descentralizadaOliveira, Bráulio César de 08 March 2016 (has links)
Submitted by Renata Lopes (renatasil82@gmail.com) on 2017-01-09T11:36:05Z
No. of bitstreams: 1
brauliocesardeoliveira.pdf: 2150243 bytes, checksum: 62faa254539b7873aa1393d8cd8f1bf2 (MD5) / Approved for entry into archive by Diamantino Mayra (mayra.diamantino@ufjf.edu.br) on 2017-01-31T11:23:24Z (GMT) No. of bitstreams: 1
brauliocesardeoliveira.pdf: 2150243 bytes, checksum: 62faa254539b7873aa1393d8cd8f1bf2 (MD5) / Made available in DSpace on 2017-01-31T11:23:24Z (GMT). No. of bitstreams: 1
brauliocesardeoliveira.pdf: 2150243 bytes, checksum: 62faa254539b7873aa1393d8cd8f1bf2 (MD5)
Previous issue date: 2016-03-08 / O presente trabalho tem por objetivo apresentar uma metodologia para estimação de estados em sistemas de distribuição de energia elétrica. São utilizadas como variáveis de estado as correntes nos ramos. As medições são obtidas por meio de medições fasoriais sincronizadas(PhasorMeasurementUnits-PMUs),sendoqueostiposdemedidasadvindos desses equipamentos são as tensões nodais e as correntes nos ramos. A abordagem é trifásica, portanto representa as características próprias de um sistema de distribuição. A metodologia consiste em resolver um problema de otimização não linear cuja função objetivo associa o erro quadrático das medidas em relação aos estados estimados sujeito às restrições de carga das barras da rede que não possuem PMUs instaladas baseadas em estimativas de cargas obtidas para o instante “t-1”, partindo-se da premissa que em curtos intervalos de tempo a carga não sofre grandes variações, sendo esta em conjunto com a abordagem trifásica as principais contribuições deste trabalho. Outra contribuição do trabalho é a descentralização, com esta técnica pode-se dividir uma determinada rede em vários subsistemas que podem ser resolvidos de forma separada e independente. Isso torna o processo mais rápido do ponto de vista computacional além de permitir o uso do processamento paralelo, visto que já existe um paralelismo natural entre as tarefas que devem ser resolvidas. Outra vantagem da divisão em subsistemas reside no fato do monitoramento de áreas de interesse. Para utilizar a descentralização foi proposta uma alternativa de alocação de PMUs que consiste em posicionar duas unidades em cada ramificação do sistema, uma no começo e outra no final do trecho, procurando utilizar o menor número possível e que não comprometa a qualidade dos estados estimados. A resolução do problema de otimização é realizada através da implementação computacional do Método de Pontos Interiores com Barreira de Segurança (Safety Barrier Interior Point Method - SFTB - IPM) proposto na literatura especializada. As medidas das PMUs foram obtidas através de um Fluxo de Potência Trifásico via Injeção de Correntes (FPTIC). Foram realizadas diversas simulações variando-se o percentual da carga e os resultados obtidos foram comparados com outra metodologia existente na literatura e com os valores verdadeiros que foram obtidos através do FPTIC para as barras não monitoradas. Foram tambémcomparadosotempocomputacionalentreaexecuçãoserialeaexecuçãoutilizando o processamento paralelo. Os testes mostraram bons resultados o que torna a metodologia proposta aplicável na supervisão de sistemas de distribuição. / This work aims to present a methodology for static state estimation in electric power distribution systems. Branch currents are used as state variables. Measurements are obtained by means of Phasor Measurement Units (PMUs), in which voltage and current branches measurements are used. The approach is three-phase, thus represents the distribution system characteristics. The methodology consists of solving a nonlinear optimization problem minimizing a quadratic objective function associated with the estimated measurements and states subject to load constraints for the non monitored loads based on estimated load obtained from the ‘t-1’ instant, starting from the assumption that in short time intervals the load does not have large variations, which together with the the three-phase approach are the main contributions of this work. Another contribution of this work is the descentralided approach, with this assumption the network can be divided into several subnetworks that can be solved separately and independently. This speeds up the process of being solved from a computational point of view and allows the use of parallel processing, since there is already a natural parallelism among tasks to be solved. Another advantage of the division into subsystems is the fact that the monitoring areas of interest. With the aim of allowing the decentralization was proposed PMUs allocation strategy that consists of allocating two units for each lateral feeder, one at the beginning and one at the end, trying to use as little PMUs as possible in such a way that the quality of the estimated states are not compromised. The resolution of the optimization problem is done through a computer implementation of Interior Point Method with Security Barrier (SFTB - IPM) proposed in the literature. The PMUs measurements were emulated using a Three-PhasePowerFlowusingtheCurrentInjectionmethod(FPTIC).Severalsimulations were performed varying the load percentage and the results obtained were compared with other existing methodology in literature and also the true values that were obtained from the FPTIC to non monitored loads. The computational time using serial and parallel processing were also compared. Results show good results which makes the proposed methodology applicable in monitoring distribution systems.
|
34 |
A Networked Control Systems Framework for Smart Grids with Integrated CommunicationSivaranjani, S January 2014 (has links) (PDF)
Over the last decade, power systems have evolved dramatically around the world, owing to higher demand, stringent requirements on quality and environmental concerns that are becoming increasingly critical. With the introduction of new technologies like large-scale renewable energy, wide-area measurement based on phasor measurement units (PMUs) and consumer interaction in the distribution system, the power grid today has become more potent than ever before. Most of the defining features of the smart grid today rest on the integration of advanced communication capabilities into the grid. While communication infrastructure has become a key enabler for the smart grid, it also introduces new and complex control challenges that must be addressed.
As we increasingly rely on information transmitted to distant areas over communication networks, it becomes imperative to model the effects of the communication system on the stability of the power grid. Several approaches exist in control theory to study such systems, widely referred to as Networked Control Systems (NCS). Networked control theory provides mathematical tools for system stability analysis and control in the presence of communication delays, packet dropouts and disordering due to transmission of sensor and actuator signals via a limited communication network.
In this thesis, a networked control framework for smart grids with integrated commu-nication infrastructure (ICT) is developed. In particular, a networked control systems perspective is developed for two scenarios - wide-area monitoring control, and coordinated control of distributed generation sources. The effects of communication delays and packet dropouts on power system stability are modeled in detail.
In the wide-area monitoring control problem, system state measurements are trans-mitted from remote locations through a communication network. The system is modeled as an NCS and a control design approach is presented to damp inter-area oscillations arising from various power system disturbances in the presence of communication constraints.
In the coordinated control scenario, a power system with geographically dispersed sources is modeled as an NCS. A networked controller is designed to stabilize the system in the presence of small signal disturbances when system measurements are subject to communication delays and packet dropouts. A realistic output feedback networked control scheme that only uses voltage measurements from PMUs is also developed for practical implementation.
The networked controllers designed in this thesis are validated against controllers designed by standard methods, by simulation on standard test systems. The networked controllers are found to enhance power system stability and load transfer capability even in the presence of severe packet dropouts and delays. Several extensions and theoretical problems motivated by this thesis are also proposed.
|
Page generated in 0.0577 seconds