Analys av fördelningssystem för bostadshus

Larsson, Johan January 2012 (has links)
The purpose of this project is to analyze earthing systems for houses. By practical measurements and theoretical analyzes consequences of possible faults, that can occur within the facility and in the low-voltage distribution network, is illustrated.   The reason for this project is that nowadays one has to arrange with a main equipotential bonding system for buildings. Apart from that, if necessary, bathrooms must be provided with a supplementary equipotential bonding system. The practical measurements verify that potential differences in facilities may be due to voltage drops in the PEN conductor between the origin of the electrical installation and the power transformer. Based on the theoretical analyzes of possible faults, it is considered that the requirement for  supplementary equipotential bonding systems for bathrooms in most cases can be questioned, when basic insulation, fault protection, residual current devise and main equipotential bonding system already provides an adequate level of protection. A PEN conductor loss may result in a situation where metallic parts attached to the equipotential bonding system starts working as earth electrodes. Equipotential bonding system may also increase the incidence of stray currents. If TN-C-S systems is provided with a local connection to earth a redundant system against PEN conductor loss is obtained. That is not the case for neutral conductor loss in TN-S systems with a local connection to earth. If district heating pipes is supplied with insulated flanges it prevents stray currents and foreign potential to be spread in the district heating network.
2

Utvärdering av elektriska fördelningssystem i medicinska utrymmen / Investigation of electric distribution systems in medical areas

Karlsson, Anders January 2015 (has links)
Detta examensarbete har utförts genom ÅF Industry i Trollhättan. Syftet med arbetet är att jämföra två elektriska fördelningssystem i medicinska utrymmen. I sjukhusmiljöer är tillgängligheten av elförsörjning av största vikt. Spänningsbortfall för livsuppehållande utrustning kan få förödande konsekvenser för berörd patient. Svensk standard förespråkar TN-S-system gentemot den europeiska standarden som anser att IT-system är mest lämpligt i dessa utrymmen. Genom att belysa dessa två systems för- och nackdelar kan ett samlat underlag sammanställas som senare används som beslutsunderlag för framtida kunder. Examensarbetet exemplifieras på Östra sjukhuset där befintligt IT-system skall uppgraderas.Skillnaden mellan dessa två fördelningssystem är deras förbindelse med jordpotential. TN-S-system har direkt förbindelse med jord jämfört med IT-system som är helt eller delvis isolerat från jord. Jordfel i TN-S-system kan generera höga felströmmar vilket kan jämföras med IT-system där minimal felström uppstår vid isolationsfel. IT-system och dess isolationsövervakningssystem kan dock anses som mer komplext jämfört med TN-S som är ett vanligare och mer vedertaget fördelningssystem i Sverige.Rapporten konstaterar att IT-system har en stor fördel gentemot TN-S-system. Anledningen är att eventuella jordfelsströmmar i TN-S-system kan bli så pass höga att säkring eller jordfelsbrytare riskerar frånkoppla fördelningssystemet. Denna problematik existerar inte i IT-system då endast små felströmmar uppstår vid isolationsfel. Rekommendationen är att bestycka dessa utrymmen med IT-system med tillhörande isolationsövervakning. Denna tekniska lösning medför tillfredsställande person- och patientsäkerhet med avseende mot elsäkerheten. / This bachelor thesis has been carried out at AF Industry. The purpose of the thesis is to compare two electric distribution systems for medical areas. In medical areas the availability of electric power always has to be maintained. Power failure of life supporting equipment will generate major risks to the patient in question. Swedish standard promotes TN-S-systems compared to the European standard that promotes IT-systems for medical areas. By comparing the advantage and disadvantage of these two systems there can be a complete report compiled, which purpose is to be used to support decision making for future customers. This bachelor thesis will be exemplified in Östra sjukhuset where existing IT-systems will be upgraded.The basic difference between these two electric power systems is their connection to earth. TN-S-systems has direct connection to earth compared to IT-systems that has none or partially connection with earth. Earth fault in TN-systems can generate major current compared to IT-systems where isolations fault generates minimal current. However IT-systems and their isolation monitoring systems might appear as a more complex system compared to TN-S which is a more accepted system in Sweden.The report states that IT-systems has major advantage against TN-systems. The reason is that potential earth fault currents in TN-S-systems might end up disconnecting the fuse or residual current breaker of affected distribution system. This issue doesn't exist in IT-systems where minor fault current is generated from isolation fault. Therefore the recommendation is to equip these medical areas with IT-systems and the associated insulation monitoring systems. This technical solution provides adequate safety for both personal and patients regarding to electrical safety.
3

Utredning av för- och nackdelar med TN-S respektive TN-C system / Investegation of the advantages and disadvantages of TN-S and TN-C systems

Alameddine, Raged, Dashtbozorg, Sajad January 2016 (has links)
I denna rapport analyseras för- och nackdelar med eldistributionssystem av typ TN-C (fyrledarsystem) respektive TN-S (femledarsystem) system. Det finns olika uppfattningar om vilket system som är lämpligast att bygga ut i distributionsnätet (lågspänningsnätet) och i fastigheternas huvudledning. Med hjälp av litteraturstudier och kontakt med olika elföretag och elbolag har olika ståndpunkter diskuterats och därefter har en sammanställning av resultatet tagits fram. Enligt analysen är TN-C det lämpligaste alternativet att använda i distributionsnätet och TN-S bör användas i fastighetens huvudledning. Detta för att kunna uppnå en god och stabil elmiljö. Detta examensarbete skall underlätta val av teknik och förhoppningsvis öka kunskapen angående ämnet. / In this report analysis the advantages and disadvantages of the TN-C (four conductor system) and TN-S (five conductor system) system. There are different opinion about which system is most appropriate to use in the distribution network and the building main lines. With the help of literature studies and contacts with various power companies and electric companies different opinion have been discussed . TN-C is the most appropriate option in the distribution network and TN-S should be used in the building main lines. This for achieving high and stable electrical environment. This thesis will facilitate the choice of technology and hopefully increase the knowledge about the subject.