Return to search

Vibration analysis of a fast response brushless excitation system

The aim of this study is to measure and analyze vibrations on a fast response brushless exciter (FRBE) at a real hydropower plant and identify vibration origins through frequency analysis. Moreover, the observed vibrations are evaluated in relation to generator vibration standards and estimated tangential eigenfrequencies of the studied FRBE. It is concluded that the pulsations in the air gap torque, originating from the rotating thyristor bridge rectifier, is the source of the strongest vibrations. Some additional vibration sources are also identified. The requirements of the generator vibration standards are mostly fulfilled and no tangential eigenfrequencies are triggered in the vibration recordings. For further studies it is recommended that alternative control strategies and optimization of the FRBE mechanical design, with respect to its ability to withstand vibrations, should be investigated.

Identiferoai:union.ndltd.org:UPSALLA1/oai:DiVA.org:uu-394098
Date January 2019
CreatorsPålsson, Emma
PublisherUppsala universitet, Elektricitetslära
Source SetsDiVA Archive at Upsalla University
LanguageEnglish
Detected LanguageEnglish
TypeStudent thesis, info:eu-repo/semantics/bachelorThesis, text
Formatapplication/pdf
Rightsinfo:eu-repo/semantics/openAccess
RelationUPTEC STS, 1650-8319 ; 19045

Page generated in 0.0012 seconds