Análise da eficiência do sistema de vedação da fundação em granito de uma barragem de concreto.

Programa de Pós-Graduação em Engenharia Geotécnica. Núcleo de Geotecnia, Escola de Minas, Universidade Federal de Ouro Preto. / Submitted by Oliveira Flávia (flavia@sisbin.ufop.br) on 2015-05-11T17:29:25Z
No. of bitstreams: 2
license_rdf: 22190 bytes, checksum: 19e8a2b57ef43c09f4d7071d2153c97d (MD5)
DISSERTAÇÃO_AnáliseEficiênciaSistema.pdf: 7280287 bytes, checksum: 13676d1ccafb8adaf0128c17f8abeeba (MD5) / Approved for entry into archive by Gracilene Carvalho (gracilene@sisbin.ufop.br) on 2015-05-12T13:31:18Z (GMT) No. of bitstreams: 2
license_rdf: 22190 bytes, checksum: 19e8a2b57ef43c09f4d7071d2153c97d (MD5)
DISSERTAÇÃO_AnáliseEficiênciaSistema.pdf: 7280287 bytes, checksum: 13676d1ccafb8adaf0128c17f8abeeba (MD5) / Made available in DSpace on 2015-05-12T13:31:18Z (GMT). No. of bitstreams: 2
license_rdf: 22190 bytes, checksum: 19e8a2b57ef43c09f4d7071d2153c97d (MD5)
DISSERTAÇÃO_AnáliseEficiênciaSistema.pdf: 7280287 bytes, checksum: 13676d1ccafb8adaf0128c17f8abeeba (MD5)
Previous issue date: 2015 / O Brasil possui um dos maiores parques hidrelétricos do mundo, com capacidade de geração de
energia comparado à posição da Arábia Saudita na extração de petróleo. Com isso é importante
avançar em conceitos e técnicas, indo além das metodologias já consagradas. Este estudo
aprofunda os conhecimentos sobre a eficiência de tratamentos de vedação em fundações rochosas
de barragens de concreto, com o uso de cortinas de injeção com calda de cimento. Tratamentos
como este permitem a redução do coeficiente de permeabilidade do maciço e a subpressão. Para
atestar a real eficiência dos serviços de vedação no vertedouro da UHE Jirau, ela foi realizada
através de três análises: redução do coeficiente de permeabilidade, redução da absorção de calda
de cimento e redução da subpressão. Na primeira análise, observando a permeabilidade antes
(furos de sondagem e furos obrigatórios de injeção) e depois (furos de verificação), concluiu-se
que o maciço possui boas características mecânicas e hidráulicas (mesmo com a presença de
fraturas sub-horizontais) por possuir coeficientes de permeabilidade baixos, sendo que a injeção
auxiliou em uma pequena redução deste coeficiente, passando da ordem de 10-5 para 10-6 cm/s..
Na segunda análise, através do acompanhamento pari passu de consumo de calda, observando o
maciço de forma geral, verificou-se que houve redução de absorção de calda de 27% e com isso a
atividade de injeção foi funcional. Na terceira e última análise, verificando as leituras de
piezometria, estas constataram que a subpressão não ultrapassou os limites referenciados em
projetos, porém como não foi utilizado o método racional com retroanálise, não foi quantificado o
quanto a cortina de injeção contribuiu para estes valores. De forma geral, adotando o critério de
Cruz (2004), que prescreve que fundações com coeficientes menores que 5 x 10-4 cm/s não há
necessidade de tratamento, conclui-se que as atividades de injeção na UHE Jirau poderiam ter
sido anuladas ou reduzidas, reduzindo o prazo e custo destes serviços. _______________________________________________________________________________ / ABSTRACT: Brazil has one of the largest hydroelectric parks in the world, with power generation capacity
compared to the position of Saudi Arabia in oil extraction. With this important to advance
concepts and techniques going, beyond the already established methodologies. This study deepens
the knowledge about the effectiveness of sealing treatments on rocky foundations of concrete
dams, with the use of injection curtains with mortar. Treatments such as this allow the reduction
of the mass permeability coefficient and the underpressure. To attest to the real efficiency of
sealing services in the spillway of UHE Jirau, it was performed through three analyzes: reduction
of permeability coefficient, reduced cement slurry absorption and reduction of negative pressure.
In the first analysis, observing the permeability before (boreholes and required injection holes)
and then (check holes), it was concluded that the mass has good mechanical and hydraulic
characteristics (even in the presence of sub-horizontal fractures) by has low water permeability
coefficient being helped in the injection a small reduction in this ratio, the order of 10-5 to 10-6
cm / sec .. In the second analysis, by simultaneously monituring liquid consumption
accompanying liquid consumption by observing the massive general, it was found that there was a
reduction sauce absorption of 27% and with this the injection activity was functional. The third
and final analysis, checking the readings of piezometric, they found that the negative pressure did
not exceed the limits referenced in projects, but was not used as the rational method with back
analysis, has not been quantified as the making injection membranes contributed to these values.
In general, adopting the criteria Cruz (2004), which provides that foundations with lower
coefficients than 5 x 10-4 cm / s dont need treatment, it is concluded that the injection activities
at UHE Jirau could have been canceled or reduced, reducing the time and cost of these services.

Identiferoai:union.ndltd.org:IBICT/oai:localhost:123456789/5291
Date January 2015
CreatorsLopes, Marieli Biondo
ContributorsAssis, André Pacheco
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UFOP, instname:Universidade Federal de Ouro Preto, instacron:UFOP
RightsAutorização concedida ao Repositório Institucional da UFOP pelo autor, 05/05/2015, com as seguintes condições: disponível sob Licença Creative Commons 3.0, que permite copiar, distribuir e transmitir o trabalho, desde que seja citado o autor e licenciante. Não permite o uso para fins comerciais nem a adaptação desta., info:eu-repo/semantics/openAccess